Plan Review Notes
Plan Review Notes For Permit 17100637
Permit Number 17100637
Review Stop B
Sequence Number 1
Notes
Date Text
2017-11-18 14:45:112014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100637 - CONSTRUCTION OF SPLASH PAD/
 INTERACTIVE WATER FEATURE.
 ADD: 1100 S. FLAGLER DR.
 CONT: RECREATIONAL DESIGN AND CONSTRUCTION
 TEL: 954-566-3885 / MAYRA TELLEZ
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SAT. NOV. 18/ 2017
 ACTION: DENIED
  
 1) THERE ARE 2 DIFFERENT SETS OF PLAN:
 1A) PLEASE NOTE THIS SET OF DOCUMENTS HAS THE FLORIDA
 DEPARTMENT OF HEALTH STAMPED RECEIPT OF APPLICATION BUT
 THE PLANS BY MYRTHA POOLS IS MISSING. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED. MISSING DOCUMENTS.
  
 COMMENT FROM OTHER PERMITS WITH REDUCED PLANS. ONE SET
 OF PLANS BY MYRTHA POOLS IS DRAWN TO SCALE 1:50 THEN
 THE PLANS WERE REDUCED TO FIT ON A 11 X 17 INCH SHEET
 OF PAPER. TOO SMALL TO READ AND OR SCAN FOR RECORD
 RETENTION. THIS DOES NOT MEET THE CITY OF WEST PALM
 BEACH ADMINISTRATIVE CODE 107.2.1.4 QUALITY OF PLANS.
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 1B) COMMENT FROM OTHER PERMITS WHERE PLANS WERE
 REDUCED. THE SET OF PLANS BY MYRTHA POOLS IS SIGNED AND
 SEALED BY JOHN E. IRELAND, THE SIGNATURE IS A PHOTO
 COPIED SIGNATURE, THE SEAL IS REDUCED IN SIZE TO
 APPROXIMATELY 7/8 OF AN INCH IN DIAMETER.
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER,
  
 1C) THERE IS ONE SET OF PLANS THAT IS 36 INCHES IN
 LENGTH AND 2 SETS OF THE SAME DOCUMENT SHRUNK TO 24
 INCHES IN LENGTH. THESE SETS OF PLANS ARE BY A
 DIFFERENT ENGINEERING FIRM CLOWARD H2O. THE REDUCED SET
 OF PLANS BY THE ENGINEER CORROY CLOWARD P. E. ALSO HAS
 A PHOTO COPIED SIGNATURE; THE SEAL IS REDUCED IN SIZE
 TO APPROXIMATELY 1 1/4 INCH IN DIAMETER.
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER,
  
 1D) IT WOULD APPEAR FROM THE COVERSHEET WITH INDEX THE
 SUBMITTED DOCUMENTS ARE FOR MORE THAN ONE POOL AND OR
 SPA. PLEASE STRIKE ON THE INDEX SHEET AND DETAILS THAT
 ARE NOT PERTINENT TO THIS PERMIT. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES, SUCH INFORMATION
 SHALL BE SPECIFIC, TO THE TECHNICAL CODES.
  
 1E) THE ARCHITECT OF RECORD FOR THE PROJECT HAS NOT PUT
 THEIR SHOP DRAWING STAMP OF APPROVAL ON THE PLANS. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 2) SHEET W1-3.01 NOR W1-3.20 PROVIDE CODE LANGUAGE OF
 REQUIRED SIGNAGE FOR INTERACTIVE WATER FEATURES
 STATING;
 2014 FBC-B 454.1.9.8.6.13
 IN ADDITION TO THE REQUIREMENTS OF SECTION 454.1.2.3.5,
 ALL IWF( INTERACTIVE WATER FEATURES/ SPLASH PAD) POOL
 RULE SIGNS INSTALLED SHALL HAVE THE FOLLOWING ADDED IN
 ONE INCH LETTERS:
  
 ?DO NOT SWALLOW THE FOUNTAIN WATER, IT IS RECIRCULATED.
 ?
  
 ?DO NOT USE FOUNTAIN IF YOU ARE ILL WITH DIARRHEA. ?
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER