| Date |
Text |
| 2017-11-18 14:45:11 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17100637 - CONSTRUCTION OF SPLASH PAD/ |
| | INTERACTIVE WATER FEATURE. |
| | ADD: 1100 S. FLAGLER DR. |
| | CONT: RECREATIONAL DESIGN AND CONSTRUCTION |
| | TEL: 954-566-3885 / MAYRA TELLEZ |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: SAT. NOV. 18/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THERE ARE 2 DIFFERENT SETS OF PLAN: |
| | 1A) PLEASE NOTE THIS SET OF DOCUMENTS HAS THE FLORIDA |
| | DEPARTMENT OF HEALTH STAMPED RECEIPT OF APPLICATION BUT |
| | THE PLANS BY MYRTHA POOLS IS MISSING. 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. MISSING DOCUMENTS. |
| | |
| | COMMENT FROM OTHER PERMITS WITH REDUCED PLANS. ONE SET |
| | OF PLANS BY MYRTHA POOLS IS DRAWN TO SCALE 1:50 THEN |
| | THE PLANS WERE REDUCED TO FIT ON A 11 X 17 INCH SHEET |
| | OF PAPER. TOO SMALL TO READ AND OR SCAN FOR RECORD |
| | RETENTION. THIS DOES NOT MEET THE CITY OF WEST PALM |
| | BEACH ADMINISTRATIVE CODE 107.2.1.4 QUALITY OF PLANS. |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| | |
| | 1B) COMMENT FROM OTHER PERMITS WHERE PLANS WERE |
| | REDUCED. THE SET OF PLANS BY MYRTHA POOLS IS SIGNED AND |
| | SEALED BY JOHN E. IRELAND, THE SIGNATURE IS A PHOTO |
| | COPIED SIGNATURE, THE SEAL IS REDUCED IN SIZE TO |
| | APPROXIMATELY 7/8 OF AN INCH IN DIAMETER. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| | SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| | DIAMETER, |
| | |
| | 1C) THERE IS ONE SET OF PLANS THAT IS 36 INCHES IN |
| | LENGTH AND 2 SETS OF THE SAME DOCUMENT SHRUNK TO 24 |
| | INCHES IN LENGTH. THESE SETS OF PLANS ARE BY A |
| | DIFFERENT ENGINEERING FIRM CLOWARD H2O. THE REDUCED SET |
| | OF PLANS BY THE ENGINEER CORROY CLOWARD P. E. ALSO HAS |
| | A PHOTO COPIED SIGNATURE; THE SEAL IS REDUCED IN SIZE |
| | TO APPROXIMATELY 1 1/4 INCH IN DIAMETER. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| | SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| | DIAMETER, |
| | |
| | 1D) IT WOULD APPEAR FROM THE COVERSHEET WITH INDEX THE |
| | SUBMITTED DOCUMENTS ARE FOR MORE THAN ONE POOL AND OR |
| | SPA. PLEASE STRIKE ON THE INDEX SHEET AND DETAILS THAT |
| | ARE NOT PERTINENT TO THIS PERMIT. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES, SUCH INFORMATION |
| | SHALL BE SPECIFIC, TO THE TECHNICAL CODES. |
| | |
| | 1E) THE ARCHITECT OF RECORD FOR THE PROJECT HAS NOT PUT |
| | THEIR SHOP DRAWING STAMP OF APPROVAL ON THE PLANS. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 2) SHEET W1-3.01 NOR W1-3.20 PROVIDE CODE LANGUAGE OF |
| | REQUIRED SIGNAGE FOR INTERACTIVE WATER FEATURES |
| | STATING; |
| | 2014 FBC-B 454.1.9.8.6.13 |
| | IN ADDITION TO THE REQUIREMENTS OF SECTION 454.1.2.3.5, |
| | ALL IWF( INTERACTIVE WATER FEATURES/ SPLASH PAD) POOL |
| | RULE SIGNS INSTALLED SHALL HAVE THE FOLLOWING ADDED IN |
| | ONE INCH LETTERS: |
| | |
| | ?DO NOT SWALLOW THE FOUNTAIN WATER, IT IS RECIRCULATED. |
| | ? |
| | |
| | ?DO NOT USE FOUNTAIN IF YOU ARE ILL WITH DIARRHEA. ? |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |