| 2017-11-18 13:48:17 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17100635 - CONSTRUCTION OF WOMENS NEW |
| | JACUZZI. |
| | ADD: 1100 S. FLAGLER DR. |
| | CONT: RECREATIONAL DESIGN AND CONSTRUCTION |
| | TEL: 954-566-3885 / MAYRA TELLEZ |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: SAT. NOV. 18/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THERE ARE 3 DIFFERENT SETS OF PLAN: |
| | 1A) ONE SET OF PLANS BY MYRTHA POOLS IS DRAWN TO SCALE |
| | 1:50 THEN THE PLANS WERE REDUCED TO FIT ON A 11 X 17 |
| | INCH SHEET OF PAPER. TOO SMALL TO READ AND OR SCAN FOR |
| | RECORD RETENTION. THIS DOES NOT MEET THE CITY OF WEST |
| | PALM BEACH ADMINISTRATIVE CODE 107.2.1.4 QUALITY OF |
| | PLANS. 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| | |
| | 1B) THE SET OF PLANS BY MYRTHA POOLS IS SIGNED AND |
| | SEALED BY JOHN E. IRELAND, THE SIGNATURE IS A PHOTO |
| | COPIED SIGNATURE, THE SEAL IS REDUCED IN SIZE TO |
| | APPROXIMATELY 7/8 OF AN INCH IN DIAMETER. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| | SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| | DIAMETER, |
| | |
| | 1C) THERE IS ONE SET OF PLANS THAT IS 36 INCHES IN |
| | LENGTH AND 2 SETS OF THE SAME DOCUMENT SHRUNK TO 24 |
| | INCHES IN LENGTH. THESE SETS OF PLANS ARE BY A |
| | DIFFERENT ENGINEERING FIRM CLOWARD H2O. THE REDUCED SET |
| | OF PLANS BY THE ENGINEER CORROY CLOWARD P. E. ALSO HAS |
| | A PHOTO COPIED SIGNATURE; THE SEAL IS REDUCED IN SIZE |
| | TO APPROXIMATELY 1 1/4 INCH IN DIAMETER. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| | SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| | DIAMETER, |
| | |
| | 1D) PLEASE PROVIDE A NARRATIVE WHY THERE ARE 2 DESIGN |
| | TEAMS ON THE SAME PROJECT? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. IF ONE IS A DELEGATE ENGINEER |
| | THEN THE ENGINEER NEEDS TO AFFIX A SHOP DRAWING STAMP |
| | OF APPROVAL ON THE DOCUMENTS. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 1E) IT WOULD APPEAR FROM THE COVERSHEET WITH INDEX THE |
| | SUBMITTED DOCUMENTS ARE FOR MORE THAN ONE POOL AND OR |
| | SPA. PLEASE STRIKE ON THE INDEX SHEET AND DETAILS THAT |
| | ARE NOT PERTINENT TO THIS PERMIT. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES, SUCH INFORMATION |
| | SHALL BE SPECIFIC, TO THE TECHNICAL CODES. |
| | |
| | 1F) SHEET W1-4.01 SHOWS VARIOUS DETAILS A,B, & C TO BE |
| | FOUND ON SHEET W1-4.20. THESE DETAILS PROVIDE CUT |
| | SECTIONS FOUND ON SHEET W5-01.09 DETAILS 1-5 SHOW WALL |
| | FRAMING MEMBERS. NONE OF THESE DETAILS PROVIDE THE TYPE |
| | OF MATERIAL THE FRAMING MEMBERS AROUND THE POOL AND |
| | BETWEEN THE POOL AND THE HOT SPA. NEITHER DOES THE PLAN |
| | INDICATE THE CENTER TO CENTER DIMENSION OF THE FRAMING |
| | MEMBERS, BRACING OR |
| | THE TYPE OF ANCHORS, SIZE OF ANCHORS TO BE INSTALLED TO |
| | LOCK THE FRAMING MEMBER IN PLACE. TO DATE NO |
| | ENGINEERING HAS BEEN SUBMITTED FOR THIS SYSTEM, THE |
| | BACKING MATERIAL THE LINER OF THE POOL SEALS AGAINST. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1G) THE ARCHITECT OF RECORD FOR THE PROJECT HAS NOT PUT |
| | THEIR SHOP DRAWING STAMP OF APPROVAL ON THE PLANS. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | 2) SHEET W5-1.09 DETAIL 5 SHOWS THE FRAME WORK WALL BUT |
| | THE PLANS ARE SILENT TO WHAT MATERIAL THE SPA IS MADE |
| | OF, THE DETAIL SHOW STAIRS BUT DOES NOT INDICATE IF |
| | THIS IS A PREFAB UNIT? 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. WILL THERE BE TILE ADHERED TO THE SURFACE |
| | BELOW? |
| | |
| | 3) NOTICE! FLORIDA DECLARATORY STATEMENT DS |
| | 2013-011CONCLUSION (2) SWIMMING POOLS THAT ARE PART OF |
| | THE COMMON USE AREAS OF MULTIFAMILY RESIDENTIAL |
| | DEVELOPMENTS THAT DO NOT RECEIVE GOVERNMENTAL FINANCIAL |
| | ASSISTANCE OR SPONSORSHIP, AND WHOSE FACILITIES ARE |
| | INTENDED SOLELY FOR THE USE OF RESIDENTS AND THEIR |
| | GUEST, ARE NOT SUBJECT THE ACCESSIBILITY CODE, |
| | INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES |
| | EVEN IF THEY ARE CONSIDERED TO FALL WITHIN THE |
| | DEFINITION OF PUBLIC SWIMMING POOLS OR PUBLIC POOLS IN |
| | SECTION 424.1.1 OF THE FBC-BUILDING. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |