| 2017-10-18 12:57:44 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #17100620 | | | MASTER #17060956 | | | 10/18/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IN ACCORDANCE WITH THE SECTION 714.4.1.1 FBC-14 | | | BUILDING, THE DUCT PENETRATING THE FIRE-RATED | | | HORIZONTAL FLOOR/CEILING ASEMBLY SHALL BE STEEL. THE | | | FLEX DUCT CANNOT BE USED AND MUST BE REMOVED AND | | | REPLACED. | | | | | | 2) PROVIDE A PRODUCT DATA SHEET FOR THE FIRESTOP SYSTEM | | | TO BE USED TO SEAL THE DUCT PENETRATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|