Plan Review Notes
Plan Review Notes For Permit 17100620
Permit Number 17100620
Review Stop M
Sequence Number 1
Notes
Date Text
2017-10-18 12:57:441ST REVIEW FBC-2014 MECHANICAL
 REVISION #17100620
 MASTER #17060956
 10/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN ACCORDANCE WITH THE SECTION 714.4.1.1 FBC-14
 BUILDING, THE DUCT PENETRATING THE FIRE-RATED
 HORIZONTAL FLOOR/CEILING ASEMBLY SHALL BE STEEL. THE
 FLEX DUCT CANNOT BE USED AND MUST BE REMOVED AND
 REPLACED.
  
 2) PROVIDE A PRODUCT DATA SHEET FOR THE FIRESTOP SYSTEM
 TO BE USED TO SEAL THE DUCT PENETRATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  