Plan Review Notes
Plan Review Notes For Permit 17100613
Permit Number 17100613
Review Stop P
Sequence Number 1
Notes
Date Text
2017-10-27 15:59:121ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR
  
 4. PLEASE PROVIDE INSIDE DIMENSION OS SHOWERS SHALL
 COMPLY WITH FBC ACC 608.2.1 / 608.2.2 / 608.2.3
  
 5. PLEASE PROVIDE CLEAR FLOOR SPACE FOR SHOWER IN UNIT
 110 PER FBC ACC 608.2.2.1 A 30 INCH WIDE MINIMUM BY 60
 INCH LONG MINIMUM CLEARANCE SHALL BE PROVIDED ADJACENT
 TO THE OPEN FACE OF THE SHOWER COMPARTMENT.
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.1 /
 608.5.2 / 608.5.3
  
 7. SHT. A801.2 DETAIL #2 THE KITCHENETTE SINK SHALL
 COMPLY WITH FBC ACC 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8. ARE THE GRAB BARS IN THE BATHROOM ENTERED INTO
 THROUGH A PRIVATE OFFICE GOING TO BE INSTALLED IF NOT
 PLEASE PROVIDE DETAIL SHOWING THE BACKING MOUNTING
 HEIGHT. PER FBC ACC 604.5 EXCEPTION 1.
  
 9. THE WATTS LFMMV THERMOSTATIC MIXING VALVE THAT IS
 SHOWN ON THE PLAN AT WATER HEATER CANNOT BE USED TO
 SUPPLY TEMPERED BY ITSELF TO THE LAVATORY'S TO MEET THE
 REQUIREMENT OF TEMPERED WATER. PER MANUFACTURE
 SPECIFICATION WARNING.
  
 10. A BACKFLOW IS REQUIRED ON REFRIGERATOR ICE MACHINE
 WATER SUPPLY PER FBC PL 608.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER