Plan Review Notes
Plan Review Notes For Permit 17100613
Permit Number 17100613
Review Stop M
Sequence Number 1
Notes
Date Text
2017-10-30 12:14:031ST REVIEW FBC-2014 MECHANICAL
 REVISION #17100613
 MASTER #17060278
 10/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M0.2: THE OUTDOOR AIR CALCULATIONS FOR RETAIL 107 DO
 NOT MATCH THE FLOOR PLANS, AND AHU-2 IS NOT SHOWN IN
 THE CALCS.
  
 2) M1.6: KITCHENETTES REQUIRE EXHAUST VENTILATION AT A
 RATE OF 0.30 CFMS PER SQ. FT.- TABLE 6-4 ASHRAE
 62.1-2010.
  
 3) M1.6: KEY NOTE #10 IS SHOWN ON THE FLOOR PLAN BUT
 NOT IN THE NOTES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER