| Plan Review Notes For Permit 17100613 |
| Permit Number |
17100613 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-30 12:14:03 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #17100613 | | | MASTER #17060278 | | | 10/30/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M0.2: THE OUTDOOR AIR CALCULATIONS FOR RETAIL 107 DO | | | NOT MATCH THE FLOOR PLANS, AND AHU-2 IS NOT SHOWN IN | | | THE CALCS. | | | | | | 2) M1.6: KITCHENETTES REQUIRE EXHAUST VENTILATION AT A | | | RATE OF 0.30 CFMS PER SQ. FT.- TABLE 6-4 ASHRAE | | | 62.1-2010. | | | | | | 3) M1.6: KEY NOTE #10 IS SHOWN ON THE FLOOR PLAN BUT | | | NOT IN THE NOTES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|