| 2017-11-06 16:39:03 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. PLEASE EXPLAIN DISCREPANCY BETWEEN ADDRESSES ON THE |
| | PROPERTY APPRAISER WEBSITE AND PLANS. THE UNIT NUMBERS |
| | ON THE PLANS DO NOT CORRELATE WITH THE UNIT NUMBERS ON |
| | THE REVISIONS. |
| | |
| | IF YOU WOULD LIKE TO HAVE THE ADDRESSES CHANGED, PLEASE |
| | CONTACT [email protected]. |
| | |
| | 2. UNITS 107 AND 108 ARE BEING COMBINED; DID YOU FILE A |
| | UNITY OF TITLE? |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 3. THE MEZZANINES AS BUILT LACKED VERTICAL |
| | ACCESSIBILITY. I HAVE NOT RESEARCHED WHY THIS IS THE |
| | CASE, BUT IT MAY BE DUE TO THE EXEPTION WHICH EXEMPTS |
| | AREAS NOT OPEN TO THE PUBLIC, OCCUPANT LOAD LESS THAN |
| | 5. |
| | |
| | FBC A 201.1.1, SHEET 203, OCCUPANT LOAD NOW EXCEEDS 5. |
| | WHY HAS VERTICAL ACCESSIBILITY TO THE ALTERED AREA NOT |
| | BEEN PROVIDED? SEE FBC 202.4.1. IF CLAIMING |
| | DISPROPORTIONATE COST, PROVIDE DOCUMENTATION VIA EMAIL |
| | PRIOR TO RESUBMITTING. |
| | |
| | 4. DETAILS 1 AND 2, IT APPEARS THAT THE PLAN DETAIL |
| | LABELS ARE REVERSED. |
| | |
| | 5. SEE FBC A 604.5 AND EXCEPTION; BACKING REQUIRED TO |
| | BE LOCATED TO PERMIT INSTALLATION OF GRAB BARS |
| | COMPLYWING WITH 604.5. IT IS NOT CLEAR WHERE THE SIDE |
| | WALL GRAB BAR WOULD BE REQUIRED, AND IT IS NOT CLEAR IF |
| | A 36" GRAB BAR WILL FIT ON THE REAR. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. |
| | |
| | 6. RESTROOM 106, SHEET A206, THE TURNING RADIUS APPEARS |
| | TO GO INTO A CABINET, CLARIFY, FBC 107. |
| | |
| | |
| | |
| | |