2017-11-06 16:39:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLEASE EXPLAIN DISCREPANCY BETWEEN ADDRESSES ON THE
 PROPERTY APPRAISER WEBSITE AND PLANS. THE UNIT NUMBERS
 ON THE PLANS DO NOT CORRELATE WITH THE UNIT NUMBERS ON
 THE REVISIONS.
  
 IF YOU WOULD LIKE TO HAVE THE ADDRESSES CHANGED, PLEASE
 CONTACT [email protected].
  
 2. UNITS 107 AND 108 ARE BEING COMBINED; DID YOU FILE A
 UNITY OF TITLE?
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. THE MEZZANINES AS BUILT LACKED VERTICAL
 ACCESSIBILITY. I HAVE NOT RESEARCHED WHY THIS IS THE
 CASE, BUT IT MAY BE DUE TO THE EXEPTION WHICH EXEMPTS
 AREAS NOT OPEN TO THE PUBLIC, OCCUPANT LOAD LESS THAN
 5.
  
 FBC A 201.1.1, SHEET 203, OCCUPANT LOAD NOW EXCEEDS 5.
 WHY HAS VERTICAL ACCESSIBILITY TO THE ALTERED AREA NOT
 BEEN PROVIDED? SEE FBC 202.4.1. IF CLAIMING
 DISPROPORTIONATE COST, PROVIDE DOCUMENTATION VIA EMAIL
 PRIOR TO RESUBMITTING.
  
 4. DETAILS 1 AND 2, IT APPEARS THAT THE PLAN DETAIL
 LABELS ARE REVERSED.
  
 5. SEE FBC A 604.5 AND EXCEPTION; BACKING REQUIRED TO
 BE LOCATED TO PERMIT INSTALLATION OF GRAB BARS
 COMPLYWING WITH 604.5. IT IS NOT CLEAR WHERE THE SIDE
 WALL GRAB BAR WOULD BE REQUIRED, AND IT IS NOT CLEAR IF
 A 36" GRAB BAR WILL FIT ON THE REAR.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
 6. RESTROOM 106, SHEET A206, THE TURNING RADIUS APPEARS
 TO GO INTO A CABINET, CLARIFY, FBC 107.
  
  
  
  