2018-02-22 13:35:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE FOR THE SALES FLOOR
 AREA. FBC CE 405.2.2, 405.2.2.2 (NOT SHOWN ON PLAN.)
 3. CORRECTED.
 4. TIME CLOCK SPECIFIED IS NOT ASTRONOMICAL TYPE.
 ENERGY CODE STATES: "LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS. FBC CE 405.2.4" PROVIDE CORRECTION.
 (CORRECTION NOT SHOWN ON PLAN.)
 5. RISER DIAGRAM SHOWS NOTE 3 IN PANEL LS AND STATES
 THAT THE AVAILABLE FAULT CURRENT IS 62,946 AMPS. PANEL
 LS IS RATED FOR 42,000 AIC. CLARIFY AND/OR CORRECT. FBC
 107.2.1; NEC 110.10, 110.9 (CORRECTION NOT SHOWN ON
 PLAN.)
 6. EMERGENCY LIGHT IN BATHROOM SHOULD BE ON SAME
 CIRCUIT AS THE LIGHTING IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F) (CORRECTION NOT SHOWN ON
 PLAN.)
 7. CORRECTED.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  