2017-10-31 11:45:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100607
 10/31/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 LENNOX AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION AND SECTION 312.1 FBC-14 MECHANICAL.
  
 2) SHEETS S-1 & M-4: INDICATE HOW THE NEW RTU CURB WILL
 BE ATTACHED TO THE STRUCTURE- SECTION 301.15.
  
 3) M-4: INDICATE FROM WHICH CODE OR STANDARD THE DUCT
 HANGER TABLE, AND THE DUCT FITTING AND CONNECTION
 DETAILS WERE DERIVED FROM.
  
 4) A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE
 REFRIGERATION SYSTEM- SECTION 107.2.1 WPB AMENDMENTS TO
 THE FBC
  