| 2017-11-03 13:50:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. FBC CE 405.5 |
| | 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE FOR THE SALES FLOOR |
| | AREA. FBC CE 405.2.2, 405.2.2.2 |
| | 3. PROVIDE REQUIRED SHOW WINDOW OUTLET ON DEDICATED |
| | CIRCUIT WITH AUTOMATIC CONTROL PER ENERGY CODE. NEC |
| | 210.62, FBC CE 405.2.2 |
| | 4. TIME CLOCK SPECIFIED IS NOT ASTRONOMICAL TYPE. |
| | ENERGY CODE STATES: "LIGHTING NOT DESIGNATED FOR |
| | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| | ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR |
| | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN |
| | ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND |
| | THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF |
| | AT LEAST 10 HOURS. FBC CE 405.2.4" PROVIDE CORRECTION. |
| | 5. RISER DIAGRAM SHOWS NOTE 3 IN PANEL LS AND STATES |
| | THAT THE AVAILABLE FAULT CURRENT IS 62,946 AMPS. PANEL |
| | LS IS RATED FOR 42,000 AIC. CLARIFY AND/OR CORRECT. FBC |
| | 107.2.1; NEC 110.10, 110.9 |
| | 6. EMERGENCY LIGHT IN BATHROOM SHOULD BE ON SAME |
| | CIRCUIT AS THE LIGHTING IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |