Plan Review Notes
Plan Review Notes For Permit 17100607
Permit Number 17100607
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-23 11:34:322014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100607
 ADD: 831 VILLAGE BLVD. SUITE:
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-914-9848
 E-MAIL: ???????? NO E-MAIL ADDRESS PROVIDED.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 23/ 2017
 ACTION: DENIED
  
 1) IS THERE A SUITE NUMBER FOR THIS TENANT SPACE, NOT
 PROVIDED ON THE PERMIT APPLICATION NOR THE HEADER STRIP
 OF PLANS?
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) THE LS1 SHEET SHOWS THE COMMON WALL BETWEEN THE
 PUBLIX GROCERY STORE AND THE NEW PUBLIX WINE & SPIRITS
 TENANT AS AN EXISTING 2 HOUR FIRE RATED WALL. SHEET A-4
 DETAIL C3 INDICATES THE USE OF A 1 ? HOUR FIRE RATED
 ACCESS DOOR ON EACH SIDE OF THE NEW PENETRATION IN THE
 FIRE RATED WALL. IN THIS SAME DETAIL IT STATES 1 HOUR
 RATED FROM EACH SIDE. THE UL LISTING U-901 PROVIDED IN
 THE LS SHEET IS FOR A 4 HOUR FIRE RATED WALL WHICH WILL
 REQUIRE A 3 HOUR OPENING PROTECTIVE. DISCREPANCY, IN
 PLANS, 107.2.1.3 ADDITIONAL DATA. PLEASE PROVIDE ALL
 DETAILS TO BE CONSISTENT.
  
 3) THE LS1 SHEET INDICATES THE REQUIREMENT FOR 2 EXITS.
 THE PLANS SHOW THE FRONT EXIT AND THE REAR GOING
 THROUGH A STORAGE OR STOCK ROOM, THE PLANS DO NOT
 DECLARE USAGE. PLEASE PROVIDE COMPLIANCE WITH:
 2014 FLORIDA BUILDING CODE 1014.2 EGRESS THROUGH
 INTERVENING SPACES.
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 4) SHEET A-1 NOTE 24 INDICATES THE INSTALLATION OF 9/16
 INCH GLASS ON DOOR. SHEET A-4 DETAIL D4/A-4 INDICATES A
 NEW STOREFRONT GLAZING SYSTEM, DOOR AND FRAME IS TO BE
 INSTALLED. PLEASE PROVIDE CONSISTENT DETAILS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. IF A NEW STOREFRONT
 GLAZING SYSTEM IS TO BE INSTALLED PLEASE COMPLY WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
  
 4A) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5A) SHEET S-1 INDICATES THE WIND DESIGN CRITERIA AS 170
 VULT, C EXPOSURE, RISK CAT. II AND ENCLOSED BUILDING.
 WHAT IS MISSING IS THE MEAN ROOF HEIGHT PER TABLE
 1609.7.2 HEIGHT AND EXPOSURE OF THE FBC-B.
  
 5B) SHEET S-1 DOES PROVIDE A PRESSURE CHART FOR
 BUILDING ZONES 1-5. THE CHART DOES NOT INDICATE IF THE
 PRESSURES ARE IN VULT OR VASD, NEED THE MEAN ROOF
 HEIGHT, NOR DO THEY PROVIDE THE TRIBUTARY AREA THEY ARE
 CALCULATED FOR, NOT ENOUGH INFORMATION. 107.2.1.3.
  
 6A) SHEET S-1 DETAIL A-5 PROVIDES A NEW A/C CURB CUT
 AND INSTALLATION OF CURB AND ATTACHMENT TO THE ROOF
 FRAMING SYSTEM BUT NOT THE CURB TO THE UNIT ITSELF. THE
 MECHANICAL SHEET M4 DETAIL C4 PROVIDES A DETAIL AND Z
 CLIP (2) PER LONG SIDE WITH ANCHORS BUT THE DETAIL DOES
 NOT INDICATE THE WIND DESIGN CRITERIA IT WAS DESIGNED
 FOR. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 2014 FBC-B
 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND
 THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS.
  
 6B) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 7) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  