| Plan Review Notes For Permit 17100578 |
| Permit Number |
17100578 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-16 18:58:09 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: | | | IT IS NOT CLEAR WHICH APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED. ASSEMBLY SELECTED BY THE ROOFING CONTRACTOR | | | AND ASSEMBLY SELECTED BY THE ENGINEER WHO CALCULATED | | | THE RAS 117 CALCULATIONS DON'T MATCH. ROOFING | | | CONTRACTOR SELECTED ASSEMBLY ON PAGE ON PAGE 25 OF 42, | | | WHILE ENGINEER SELECTED ASSEMBLY ON PAGE 24 OF 42. THE | | | FASTENER SPACING AND THE WIDTH OF THE BASE SHEET LAP | | | ARE DIFFERENT. REVISE AS REQUIRED TO MATCH. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|