| 2017-11-17 10:18:28 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A-3 THE CALCULATIONS OF THE MINIMUM NUMBER OF |
| | PLUMBING FIXTURES ARE INCORRECT IT SHALL BE TOTAL |
| | OCCUPANT LOAD 135 = 67.5 MEN, 67.5 WOMEN = 3 WC MEN, 3 |
| | WC WOMEN, 2 LAV MEN, 2 LAV WOMEN PLEASE CORRECT. PER |
| | FBC PL SEC 403.1.1 AND TABLE 403.1 |
| | |
| | 2. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. PER FBC |
| | ACC 604.7 |
| | |
| | 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2 |
| | |
| | 4. PLEASE SHOW CLEAR FLOOR SPACE, HEIGHT AND DEPTH FOR |
| | ACCESSIBLE URINAL. PER FBC ACC 213.3.3, 605.2 AND 605.3 |
| | |
| | 5. THE WALLS AROUND THE URINAL AND MOP SINK SHALL |
| | COMPLY WITH FBC 1210.2.2 |
| | |
| | 6. A BACKFLOW IS REQUIRED ON THE WATER SUPPLY'S FOR THE |
| | ICE MACHINE AND REFRIGERATOR ICE MACHINE. PER FBC PL |
| | 608.3 |
| | |
| | 7. THE NEW WC AND FLOW DRAIN FOR ICE MACHINE SHALL BE |
| | VENTED. PER FBC PL 901.2, 901.2.1 |
| | |
| | 8.PLEASE LABEL THE HOT, COLD AND RETURN ON WATER |
| | ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. PLEASE LABEL PIPE SIZES ON THE DRAIN LINES FOR THE |
| | NEW KITCHEN AND FD. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |