| Plan Review Notes For Permit 17100554 |
| Permit Number |
17100554 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-13 12:10:51 | 1ST REVIEW FBC-2014 MECHANICAL, WPB AMENDMENTS TO THE | | | FBC. | | | PERMIT #17100554 | | | 11/13/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR | | | SYSTEMS OF THE 5-TON AC SYSTEMS PER SECTION 606.2.1. | | | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | | MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT | | | CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | 2) THREE DIFFUSERS IN CAFE 127 ARE NOT TAGGED- SECTION | | | 107.1 | | | | | | 3) THE KW OF THE HEAT STRIPS IN AHU'S 2, 3, 4, 5, 7, 8, | | | 9, 10 & 11 ARE EXCEEDING THE CALCULATED LOADS- SECTION | | | C403.2.2 FBC-14 ENERGY CONSERVATION. | | | | | | 4) ONE OF THE TWO SETS OF ENERGY AND AC CALCULATIONS IS | | | MISSING CALCULATIONS FOR SYSTEMS 5-11- SECTION 107.1. | | | | | | 5) THE REQUIRED WIND LOAD ENGINEERING FOR THE ROOFTOP | | | CONDENSERS AND STANDS WAS NOT PROVIDED. PLEASE PROVIDE | | | THE DESIGN CRITERIA AND PRESSURES ON THE PLANS, AND | | | SUBMIT THE NOA FOR THE ROOF STAND WITH SHOP DRAWING | | | APPROVAL STAMP BY THE ENGINEER OF RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|