2017-11-13 12:10:511ST REVIEW FBC-2014 MECHANICAL, WPB AMENDMENTS TO THE
 FBC.
 PERMIT #17100554
 11/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF THE 5-TON AC SYSTEMS PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 2) THREE DIFFUSERS IN CAFE 127 ARE NOT TAGGED- SECTION
 107.1
  
 3) THE KW OF THE HEAT STRIPS IN AHU'S 2, 3, 4, 5, 7, 8,
 9, 10 & 11 ARE EXCEEDING THE CALCULATED LOADS- SECTION
 C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 4) ONE OF THE TWO SETS OF ENERGY AND AC CALCULATIONS IS
 MISSING CALCULATIONS FOR SYSTEMS 5-11- SECTION 107.1.
  
 5) THE REQUIRED WIND LOAD ENGINEERING FOR THE ROOFTOP
 CONDENSERS AND STANDS WAS NOT PROVIDED. PLEASE PROVIDE
 THE DESIGN CRITERIA AND PRESSURES ON THE PLANS, AND
 SUBMIT THE NOA FOR THE ROOF STAND WITH SHOP DRAWING
 APPROVAL STAMP BY THE ENGINEER OF RECORD.
  