2017-11-15 16:02:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS THAT THERE ARE 200 AMP FEEDS TO
 PANELS LA, LB, LC, AND LD. HOWEVER, THESE PANELS ARE
 LISTED AS 100 AMP MAIN LUG ONLY PANELS, WITH MANY
 PHASES SHOWING A LOAD OF MORE THAN 100 AMPS. THIS MAY
 BE A TYPO IN THE PANEL SCHEDULE. CLARIFY AND/OR
 CORRECT. FBC 107.2.1
 2. PANEL LA-2,4,6 SHOWS A 100 AMP EXISTING CIRCUIT, BUT
 NO LOAD IS SHOWN FOR THIS IN THE PANEL SCHEDULE.
 CLARIFY AND/OR CORRECT. FBC 107.2.1, NEC 220
 3. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  