| Plan Review Notes For Permit 17100554 |
| Permit Number |
17100554 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-15 16:02:01 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. RISER DIAGRAM SHOWS THAT THERE ARE 200 AMP FEEDS TO | | | PANELS LA, LB, LC, AND LD. HOWEVER, THESE PANELS ARE | | | LISTED AS 100 AMP MAIN LUG ONLY PANELS, WITH MANY | | | PHASES SHOWING A LOAD OF MORE THAN 100 AMPS. THIS MAY | | | BE A TYPO IN THE PANEL SCHEDULE. CLARIFY AND/OR | | | CORRECT. FBC 107.2.1 | | | 2. PANEL LA-2,4,6 SHOWS A 100 AMP EXISTING CIRCUIT, BUT | | | NO LOAD IS SHOWN FOR THIS IN THE PANEL SCHEDULE. | | | CLARIFY AND/OR CORRECT. FBC 107.2.1, NEC 220 | | | 3. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C | | | EQUIPMENT PER CODE. NEC 210.63 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|