| Date |
Text |
| 2017-11-21 13:33:46 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17100530 |
| | 11/16/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENTS 2-4 FROM THE 2ND REVIEW STILL EXISTS. THE |
| | COMMENTS ARE REPRINTED BELOW-PLEASE COMPLY |
| | |
| | 1) TWO DIFFERENT SETS OF AC PLANS AND ENERGY |
| | CALCULATIONS ARE IN THIS PERMIT SUBMITTAL. THE |
| | CONTRACTOR MUST VOID OUT WHICHEVER SET OF PLANS AND |
| | CALCULATIONS ARE TO BE DISCARDED. |
| | |
| | 2) PLEASE NOTE THAT THE OWNER/AGENT'S SIGNATURE SHALL |
| | BE ON THE ENERGY COMPLIANCE FORM R405-2014- SECTION |
| | R103.1.1.2. |
| | |
| | 3) THE AC PLAN BY KO ENERGY IS INDICATING A MIAMI-DADE |
| | NOA OR FL. PRODUCT APPROVAL FOR CONDENSER CLIPS IS TO |
| | BE PROVIDED HOWEWER THE SUBMITTAL FROM ENGINEERING |
| | EXPRESS IS NEITHER ONE, AND THE DOCUMENT ALSO REQUIRES |
| | A RAISED SEAL TO BE VALID AS NOTED ON THE 1ST SHEET. |
| | |
| | 4) NO ELECTRICAL PLAN OR SUB-PERMIT WAS SUBMITTED. IF |
| | TO BE UNDER SEPARATE PERMIT PLEASE INDICATE ON THE |
| | PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |