| Plan Review Notes For Permit 17100530 |
| Permit Number |
17100530 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-16 10:19:00 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100530 | | | 11/16/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) TWO DIFFERENT SETS OF AC PLANS AND ENERGY | | | CALCULATIONS ARE IN THIS PERMIT SUBMITTAL. THE | | | CONTRACTOR MUST VOID OUT WHICHEVER SET OF PLANS AND | | | CALCULATIONS ARE TO BE DISCARDED. | | | | | | 2) PLEASE NOTE THAT THE OWNER/AGENT'S SIGNATURE SHALL | | | BE ON THE ENERGY COMPLIANCE FORM R405-2014- SECTION | | | R103.1.1.2. | | | | | | 3) THE AC PLAN BY KO ENERGY IS INDICATING A MIAMI-DADE | | | NOA OR FL. PRODUCT APPROVAL FOR CONDENSER CLIPS IS TO | | | BE PROVIDED HOWEWER THE SUBMITTAL FROM ENGINEERING | | | EXPRESS IS NEITHER ONE, AND THE DOCUMENT ALSO REQUIRES | | | A RAISED SEAL TO BE VALID AS NOTED ON THE 1ST SHEET. | | | | | | 4) NO ELECTRICAL PLAN OR SUB-PERMIT WAS SUBMITTED. IF | | | TO BE UNDER SEPARATE PERMIT PLEASE INDICATE ON THE | | | PLAN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|