2017-11-16 10:19:002ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100530
 11/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TWO DIFFERENT SETS OF AC PLANS AND ENERGY
 CALCULATIONS ARE IN THIS PERMIT SUBMITTAL. THE
 CONTRACTOR MUST VOID OUT WHICHEVER SET OF PLANS AND
 CALCULATIONS ARE TO BE DISCARDED.
  
 2) PLEASE NOTE THAT THE OWNER/AGENT'S SIGNATURE SHALL
 BE ON THE ENERGY COMPLIANCE FORM R405-2014- SECTION
 R103.1.1.2.
  
 3) THE AC PLAN BY KO ENERGY IS INDICATING A MIAMI-DADE
 NOA OR FL. PRODUCT APPROVAL FOR CONDENSER CLIPS IS TO
 BE PROVIDED HOWEWER THE SUBMITTAL FROM ENGINEERING
 EXPRESS IS NEITHER ONE, AND THE DOCUMENT ALSO REQUIRES
 A RAISED SEAL TO BE VALID AS NOTED ON THE 1ST SHEET.
  
 4) NO ELECTRICAL PLAN OR SUB-PERMIT WAS SUBMITTED. IF
 TO BE UNDER SEPARATE PERMIT PLEASE INDICATE ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  