| Plan Review Notes For Permit 17100530 |
| Permit Number |
17100530 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-24 09:57:24 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100530 | | | 10/24/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AC CONTRACTORS SIGNATURE MUST BE ON THE PLANS: | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 | | | FBC. WPB AMENDMENTS TO THE FBC. | | | | | | 2) INDICATE HOW AIR IS BEING RETURNED TO THE AIR | | | HANDLER. IS THIS AN OPEN RETURN THOUGH THE KITCHEN OR | | | WILL A RETURN GRILL BE INSTALLED IN THE HALLWAY. PLEASE | | | NOTE THAT RETURN AIR CANNOT BE TAKEN FROM A KITCHEN- | | | SECTION 918.6. | | | | | | 3) THE 6X8 TRANSFER GRILLS IN THE BEDROOMS ARE | | | UNDERSIZED PER SECTION 601.5 EXCEPTION #2- 50 SQ. | | | INCHES PER 100 CFM REQUIRED. | | | | | | 4) PROVIDE THE AC EQUIPMENT SCHEDULE ON THE PLAN. | | | | | | 5) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307. | | | | | | 5) PROVIDE AN ELECTRICAL PLAN SUB-PERMIT APPLICATION, | | | AND INCREASE THE $4500.00 VALUE LISTED ON THE MAIN | | | APPLICATION TO COVER THE ADDITIONAL EXPENSE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|