2017-10-24 09:57:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100530
 10/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CONTRACTORS SIGNATURE MUST BE ON THE PLANS:
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 FBC. WPB AMENDMENTS TO THE FBC.
  
 2) INDICATE HOW AIR IS BEING RETURNED TO THE AIR
 HANDLER. IS THIS AN OPEN RETURN THOUGH THE KITCHEN OR
 WILL A RETURN GRILL BE INSTALLED IN THE HALLWAY. PLEASE
 NOTE THAT RETURN AIR CANNOT BE TAKEN FROM A KITCHEN-
 SECTION 918.6.
  
 3) THE 6X8 TRANSFER GRILLS IN THE BEDROOMS ARE
 UNDERSIZED PER SECTION 601.5 EXCEPTION #2- 50 SQ.
 INCHES PER 100 CFM REQUIRED.
  
 4) PROVIDE THE AC EQUIPMENT SCHEDULE ON THE PLAN.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.
  
 5) PROVIDE AN ELECTRICAL PLAN SUB-PERMIT APPLICATION,
 AND INCREASE THE $4500.00 VALUE LISTED ON THE MAIN
 APPLICATION TO COVER THE ADDITIONAL EXPENSE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  