| Plan Review Notes For Permit 17100493 |
| Permit Number |
17100493 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-30 16:09:07 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100493 | | | 11/30/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE OWNER OR AGENT MUST SIGN AND DATE THE ENERGY | | | FORM R405-2014. | | | | | | 2) THE PLAN SHOWS AN OUTSIDE AIR DUCT FOR THE AC | | | SYSTEM. PLEASE PROVIDE THE COMPLIANCE DATA FOR | | | MECHANICAL VENTILATION ON PAGE 4 OF ENERGY FORM | | | R405-2014. | | | | | | 3) PLEASE SUBMIT THE FLORIDA PRODUCT APPROVAL FOR THE | | | BMP CONDENSER TIE-DOWN CLIPS. | | | | | | 4) THE AC CALCULATIONS ARE BASED ON THE FRONT DOOR | | | FACING NORTH, HOWEVER HE SITE PLAN INDICATES THE FRONT | | | DOOR OF THE HOUSE FACES SOUTH- PLEASE CORRECT THE | | | CALCULATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|