Plan Review Notes
Plan Review Notes For Permit 17100493
Permit Number 17100493
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-22 12:31:071ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL, ENERGY
 CONSERVATION
 PERMIT #17100493
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION R403.6.1 FBC-14 ENERGY CONSERVATION.
  
 2) COMPLIANCE WITH THE RESIDENTIAL PROVISION OF THE
 ENERGY CODE IS REQUIRED PER SECTION R101.5. BECAUSE THE
 AIR HANDLER IS TO BE LOCATED IN THE ATTIC, THE NEW HOME
 CANNOT BE BROUGHT INTO COMPLIANCE USING FORM R402 WHICH
 IS THE PRESCRIPTIVE METHOD - SEE SECTION R403.2.4.
 THEREFORE THE PERFORMANCE BASED METHOD SHALL BE APPLIED
 USING THE ENERGYGAUGE R405-2014 SOFTWARE PRINTOUT.
 PLEASE SUBMIT THE COMPLIANCE REPORT.
  
 3) SUBMIT THE FLORIDA PRODUCT APPROVAL FOR THE BMP
 CONDENSER TIE-DOWN CLIPS.
  
 4) PLEASE VERIFY COMPLIANCE WITH THE FOLLOWING
 PROVISIONS OF SECTION R403.2.4 AIR HANDLING UNITS:
  
 AIR HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
  
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD.
  
 5) PLEASE NOTE THAT A BLOWER DOOR TEST IS MANDATORY.
 PLEASE REVIEW SECTION R405.4.1.2 FOR MORE INFORMATION
 ABOUT TESTING.
  