| Date |
Text |
| 2017-12-18 14:19:21 | PLAN DENIED | | | 1) PROVIDE EQUIPMENT SCHEDULE ON PLAN. | | | PER SECTION 107 FBC 2014 | | | 2) ENERGY CALCULATIONS STATE DUCTLESS MINISPLIT | | | PLAN SHOWS DUCT WORK PLEASE EXPLAIN. | | | 3) PROVIDE MORE INFORMATION ON 600CFM BOASTER | | | FAN. | | | 4) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | PROVIDE A SIGNATURE ON THE PLAN OF THE PERSON WHO DREW | | | THE PLAN | | | AND TAKING RESPONSIBILITY OF THE PLAN | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|