Plan Review Notes
Plan Review Notes For Permit 17100465
Permit Number 17100465
Review Stop B
Sequence Number 2
Notes
Date Text
2018-02-13 13:11:11****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 SECOND REVIEW:
  
 1. ADDRESSED
  
  
 2. PARTIALLY COMPLIED / SEE WIND LOADS, BASIC WIND
 SPEED SHOULD BE 170 MPH/ 3 SEC GUST.
  
 PROVIDE THE WIND DESIGN DATA, FBC 1603.1.4 WIND DESIGN
 DATA.
  
 3. ADDRESSED
  
 4. NOT PROVIDED
 SPECIFY ROOFING PRODUCT USED AND PROVIDE 2 COPIES OF
 PRODUCT APPROVALS. FAC9N-3
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 5. ADDRESSED
 _______________________________________________________
 __________________
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  