Plan Review Notes
Plan Review Notes For Permit 17100465
Permit Number 17100465
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-27 10:59:55****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. PLEASE SHOW ON PLANS THE LEVEL OF ALTERATION PER FBC
 EXISTING BUILDING CODE 2014. 501.1 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL BE USED IN
 CONJUNCTION WITH CHAPTERS 6 THROUGH 13 AND SHALL APPLY
 TO THE ALTERATION, REPAIR, ADDITION AND CHANGE OF
 OCCUPANCY OF EXISTING STRUCTURES, INCLUDING HISTORIC
 AND MOVED STRUCTURES, AS REFERENCED IN SECTION 301.1.2.
 THE WORK PERFORMED ON AN EXISTING BUILDING SHALL BE
 CLASSIFIED IN ACCORDANCE WITH THIS CHAPTER.
  
 2. PROVIDE THE WIND DESIGN DATA, FBC 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCERESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF
 (KN/M2).
  
 3. SHOW THE TYPE OF CONSTRUCTION CLASSIFICATION. FBC
 602
  
 4. SPECIFY ROOFING PRODUCT USED AND PROVIDE 2 COPIES OF
 PRODUCT APPROVALS. FAC9N-3
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 5. SEE DETAIL KEY LEGEND #18 AND SHOW COMPLIANCE WITH
 FBC- R703.6.3 STUCCO
 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED TO LATH
 OVER FRAME CONSTRUCTION, MEASURES SHALL BE TAKEN TO
 PREVENT BONDING BETWEEN THE CEMENT PLASTER AND THE
 WATER-RESISTIVE BARRIER: TWO LAYERS OR ONE LAYER OF AN
 APPROVED WATER-RESISTANT BARRIER OVER AN APPROVED
 PLASTIC HOUSE WRAP, OR OTHER APPROVED METHODS IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
 _______________________________________________________
 __________________
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  