| 2017-10-21 12:17:00 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW COMPLIANCE WITH THE REAR WALL GRAB BAR SHALL BE |
| | 36 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE |
| | OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND |
| | 24 INCHES MINIMUM ON THE OTHER SIDE. PER FBC ACC |
| | 604.5.2 |
| | |
| | 2. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1 |
| | AND SHALL COMPLY WITH FBC ACC 602 IF ONE IS PROVIDED IN |
| | COMMON AREA PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 4. A BACKFLOW IS REQUIRED ON THE ICE MAKER LINE. PER |
| | FBC PL 608.3 |
| | |
| | 5. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1 |
| | IF ONE IS PROVIDED IN COMMON AREA PLEASE PLACE NOTE ON |
| | PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |