| 2017-10-26 11:11:10 | 1ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING CODE | | | PERMIT #17100401 | | | 10/26/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHOW THE ACTUAL LOCATION OF THE NEW CU-1 ON THE ROOF | | | AND PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | THE STAND AND THE CONDENSER- SECTION 301.15. | | | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|