| 2017-10-31 10:42:01 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE DETAILS OF GFCI RECEPTACLE REQUIRED ON ROOF |
| | WITHIN 25 FEET OF CU UNIT. NEC 210.63 |
| | 2. PROVIDE DETAILS OF RECEPTACLE CONTROL REQUIRED PER |
| | ASHRAE 90.1. THE NOTE SUPPLIED IS NOT ADEQUATE DETAIL, |
| | SHOW WHICH CIRCUITS/RECEPTACLES ARE CONTROLLED AND THE |
| | METHOD OF CONTROL. THE AREAS INCLUDED SHOULD BE: AT |
| | LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP RECEPTACLES IN |
| | ALL PRIVATE OFFICES, CONFERENCE ROOMS, ROOMS USED |
| | PRIMARILY FOR PRINTING AND/OR COPYING FUNCTIONS, BREAK |
| | ROOMS, CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. AT |
| | LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR |
| | MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION |
| | DOCUMENTS. ASHRAE 90.1, 8.4.2; FBC CE 405.7.1; FBC |
| | 107.2.1 |
| | 3. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | ETC.. FBC 105.1, 107.2.1 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |