Plan Review Notes
Plan Review Notes For Permit 17100392
Permit Number 17100392
Review Stop M
Sequence Number 1
Notes
Date Text
2017-10-27 15:19:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100392
 10/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MEP ENGINEERS IS NOT THE ENGINEER OF RECORD ON THE
 MAIN STORAGE BUILDING PLANS, AND THEREFORE CANNOT
 CERTIFY THE DRAWINGS FROM EXCEL FIRE PROTECTION.
 PROVIDE EITHER A SHOP DRAWING STAMP FROM THE ENGINEER
 OF RECORD, OR SIGNED AND SEALED DRAWINGS BY A FL.
 LICENSED ENGINEER IN ACCORDANCE WITH SECTION
 633.021(5)(E) FLORIDA STATUTES.
  
 2) PROVIDE THE NUMBER ADDRESS OF THE FACILITY ON THE
 PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER