Plan Review Notes
Plan Review Notes For Permit 17100375
Permit Number 17100375
Review Stop P
Sequence Number 3
Notes
Date Text
2018-01-19 17:51:213RD REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: TO EXPEDITE THE APPROVAL OF THIS
 PERMIT I SUGGESTED A MEETING ON THE SECOND REVIEW, TO
 GO OVER THE COMMENTS BUT ONE WAS NEVER REQUESTED IN
 ORDER FOR THIS PLAN TO BE APPROVED ALL COMMENTS WILL
 NEED TO BE ADDRESSED.
  
 PREVIOUS COMMENTS
 7. SHT. P-2 THE SANITARY AND WATER ISOMETRIC DRAWINGS
 ARE VERY LIGHT ON THE PLAN SHEET AND WHEN SCANNED IN
 FOR OUR RECORDS IT WILL NOT SHOW UP. THEY ARE ALSO
 DIFFICULT TO READ THEY ARE TO COMPRESSED PLEASE DARKEN
 AND EXPAND THE DIAGRAMS. PER WPB AMEND TO FBC 107.2.1
 3RD REQUEST: THE LINES OF THE ISOMETRIC ARE STILL TO
 LIGHT AND TO COMPRESSED TO DETERMINE IF THEY ARE CODE
 COMPLIANT.
  
 9. SHT. P-2 THE SANITARY PIPING FOR THE EQUIPMENT ROOM
 IS UNCLEAR PLEASE EXPAND AND SHOW THE TRAP FOR THE MOP
 SINK, TRAP FOR THE FLOOR DRAIN AND THE TRAP FOR THE
 VACUUM TANK DRAIN ALSO THE VENT FOR THESE FIXTURE.
 912.1 AND FBC PL 1002.1, 901.2.
 3RD REQUEST I AM UNABLE TO DETERMINE HOW THE PIPING IS
 BEING RUN DO TO MULTIPLE REASONS SUCH AS LINES CROSSING
 EACH OTHER THAT SHOULD NOT BE CONNECTED .LINES BEING
 DRAWN TO CLOSE TOGETHER AND FIXTURES NOT BEING LABELED.
  
 3RD REQUEST16. SHT. P-5 UNDER THE NOTES IT REFERENCES
 THE FBC 2010 THIS PROJECT IS UNDER FBC 2014 5TH EDITION
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3RD REQUEST 17. PLEASE SHOW COMPLIANCE WITH FBC PL
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY
 THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2.
 A THERMAL EXPANSION TANK OR VALVE IS REQUIRED ONE HAS
 NOT BEEN INDICATED ON PLAN.
  
  
 NEW COMMENT: 1. THE 6 GALLON HEATER DOES NOT HAVE
 ENOUGH STORAGE CAPACITY TO MAINTAIN THE REQUIRED HOT
 WATER AT EACH FIXTURE. PER FBC PL 607.1
  
 2. PLEASE LABEL ALL THE FIXTURES ON THE ISOMETRIC. PER
 WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  