Date Text
2017-10-24 10:51:081ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4
  
 2. SHT. D2 THE DETAIL FOR THE WATER FOUNTAIN IS
 ILLEGIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. D2 THE DETAIL FOR THE WATER CLOSET SINGLE USER
 . THE SKETCHES SHOWING THE CLEAR FLOOR SPACE ARE NON
 COMPLIANT PLEASE COMPLIANCE ONLY WITH FBC ACC FIGURE
 604.8.1.1
  
 4. SHT. D2 - P5 THE DETAIL FOR THE TANK PLUMBING IS
 ILLEGIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. PLEASE SHOW CLEAR FLOOR SPACE FOR LAVATORY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. PLEASE SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE FOR
 THE ACCESSIBLE FIXTURES. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. P1 THE DETAIL FOR THE REFRIGERATED AIR DRYER IS
 ILLEGIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTILLATION GUIDE FOR VACUUM PUMP , AIR COMPRESSOR AND
 DENTAL CHAIRS. PER WPB AMEND TO FBC 107.2.1
  
 9. PROVIDE A DETAIL PIPING CONNECTIONS ON VACUUM. AIR
 COMPRESSER, WATER HEATER AND DENTAL CHAIRS. PER WPB
 AMEND TO FBC 107.2.1
  
 10. SHT P4 PLEASE SEPARATE THE WATER AND SANITARY
 ISOMETRIC DRAWINGS INTO 2 SEPARATE DRAWING. PER WPB
 AMEND TO FBC 107.2.1
  
 11. SHT. P4 DIRECTIONAL FITTING ON THE VACUUM ISO ARE
 SHOWN IN THE WRONG DIRECTION PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 12. HOT WATER RECIRCULATION SYSTEM REQUIRED SHOW ON
 WATER RISER. PER FBC PL 607.2
  
 13. THE VACUUM EXHAUST SHALL COMPLY WITH NFPA 99/
 5.1.3.7.6 PLACE NOTE ON PLAN
  
 14. SHOW COMPLIANCE WITH FBC PL 403.2 SEPARATE
 FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER