Plan Review Notes
Plan Review Notes For Permit 17100375
Permit Number 17100375
Review Stop M
Sequence Number 1
Notes
Date Text
2017-10-25 14:34:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100375
 10/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: SMOKE DETECTORS ARE REQUIRED IN THE RETURN
 AIR SYSTEMS OF THE 5-TON AC SYSTEMS PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS
 ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY
 AIR.
  
 2) M1: THE EQUIPMENT ROOM MUST HAVE CONDITIONED AIR
 SUPPLIED TO IT IN ACCORDANCE WITH THE MANUFACTURER'S
 SPECIFICATIONS FOR THE OSPREY COMPRESSOR ON SHEET P1.
 PLEASE REVISE THE PLAN ACCORDINGLY.
  
 3) PLEASE CLARIFY IF ANY MED GAS WILL BE STORED ONSITE
 AND PROVIDE THE STORAGE LOCATION AND QUANTITIES OF GAS
 STORED IN THAT LOCATION- SECTION 5.1.3.3.1.7 NFPA 99.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved