| Plan Review Notes For Permit 17100375 |
| Permit Number |
17100375 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-25 14:34:32 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100375 | | | 10/25/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1: SMOKE DETECTORS ARE REQUIRED IN THE RETURN | | | AIR SYSTEMS OF THE 5-TON AC SYSTEMS PER SECTION | | | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED | | | IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS | | | ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY | | | AIR. | | | | | | 2) M1: THE EQUIPMENT ROOM MUST HAVE CONDITIONED AIR | | | SUPPLIED TO IT IN ACCORDANCE WITH THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE OSPREY COMPRESSOR ON SHEET P1. | | | PLEASE REVISE THE PLAN ACCORDINGLY. | | | | | | 3) PLEASE CLARIFY IF ANY MED GAS WILL BE STORED ONSITE | | | AND PROVIDE THE STORAGE LOCATION AND QUANTITIES OF GAS | | | STORED IN THAT LOCATION- SECTION 5.1.3.3.1.7 NFPA 99. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|