| Plan Review Notes For Permit 17100351 |
| Permit Number |
17100351 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-27 17:23:09 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100351 | | | 11/27/17 | | | | | | THE PLANS HAVE BEEN FAILED FOR A SECOND TIME DUE TO THE | | | FOLLOWING OMMISSIONS AND DEFICIENCIES. | | | | | | 1) SHEETS "DUCT" AND "DUCT-2": THE REVISED DRAWINGS DO | | | NOT SHOW THE DUCT SIZES, SEGMENT LENGTHS, TEES, WYES, | | | ETC. THE PREVIOUSLY SUBMITTED SHOP DRAWINGS SUBMITTED | | | ON SHEET "DUCT" HAD SPECIFIED ALL COMPONENTS OF THE | | | VENT ASSEMBLIES. PLEASE PROVIDE THE DRAWING OR MODIFY | | | THE CURRENT DRAWING. | | | | | | 2) SHEET DUCT-2, WIND LOAD ENGINEERING: PROVIDE MISSING | | | FASTENING DETAILS- DUCT TO FAN, AND DUCT BRACKET TO | | | ROOF STRUCTURE. | | | | | | 3) SHEET DUCT-2, ELEVATION VIEW: THE DRAWING DOES NOT | | | SHOW THE FAN AND CURB, AND THE DISCHARGE HEIGHT OF THE | | | EXHAUST FAN ABOVE THE ROOF. | | | | | | 4) SHEETS DUCT AND DUCT-2: PROVIDE THE SLOPE OF THE | | | DUCT. | | | | | | 5) SUBMIT A CUT SHEET FOR THE CAPTIVE AIRE FANS. | | | | | | 6) THE EXHAUST DUCTS RUNNING THROUGH THE PLENUM ARE NOT | | | PERMITTED UNLESS MEETING ONE OF THE EXCEPTIONS LISTED | | | UNDER SECTION 601.4. PLEASE VERIFY COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|