2017-11-27 17:23:092ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100351
 11/27/17
  
 THE PLANS HAVE BEEN FAILED FOR A SECOND TIME DUE TO THE
 FOLLOWING OMMISSIONS AND DEFICIENCIES.
  
 1) SHEETS "DUCT" AND "DUCT-2": THE REVISED DRAWINGS DO
 NOT SHOW THE DUCT SIZES, SEGMENT LENGTHS, TEES, WYES,
 ETC. THE PREVIOUSLY SUBMITTED SHOP DRAWINGS SUBMITTED
 ON SHEET "DUCT" HAD SPECIFIED ALL COMPONENTS OF THE
 VENT ASSEMBLIES. PLEASE PROVIDE THE DRAWING OR MODIFY
 THE CURRENT DRAWING.
  
 2) SHEET DUCT-2, WIND LOAD ENGINEERING: PROVIDE MISSING
 FASTENING DETAILS- DUCT TO FAN, AND DUCT BRACKET TO
 ROOF STRUCTURE.
  
 3) SHEET DUCT-2, ELEVATION VIEW: THE DRAWING DOES NOT
 SHOW THE FAN AND CURB, AND THE DISCHARGE HEIGHT OF THE
 EXHAUST FAN ABOVE THE ROOF.
  
 4) SHEETS DUCT AND DUCT-2: PROVIDE THE SLOPE OF THE
 DUCT.
  
 5) SUBMIT A CUT SHEET FOR THE CAPTIVE AIRE FANS.
  
 6) THE EXHAUST DUCTS RUNNING THROUGH THE PLENUM ARE NOT
 PERMITTED UNLESS MEETING ONE OF THE EXCEPTIONS LISTED
 UNDER SECTION 601.4. PLEASE VERIFY COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER