Date Text
2017-10-26 18:21:271ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100351
 10/26/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO PAGE 5 OF THE SUBMITTED JERMIAS EXHAUST
 SYSTEM INSTALLATION INSTRUCTIONS FOR MODEL DWKL. THE
 PIZZA OVEN EXHAUST DUCTS ARE REQUIRED TO BE ENCLOSED IN
 NON-COMBUSTIBLE CONSTRUCTION HAVING A FIRE RATING EQUAL
 TO OR GREATER THAN THAT OF THE WALL OR CEILING THROUGH
 WHICH IT PASSES. THE SUBMITTED PLAN DOES NOT DEPICT
 ACTUAL FIELD CONDITIONS BUT THE APPROVED PLANS FOR THE
 RESTAURANT UNDER PERMIT #17020623 APPEAR TO SHOW THE
 DUCTS VERTICALLY PENETRATING THE DRYWALL CEILING, AND
 THEN RUNNING HORIZONTALLY ABOVE THE CEILING TO THE
 FIRE-RATED SHAFT. PROVIDE DRAWINGS AND DETAILS THAT
 INDICATE HOW THE DUCT WILL BE ENCLOSED AS REQUIRED BY
 THE MANUFACTURER AND THE UL 1978 LISTING. PLEASE NOTE
 THAT THE JERMIAS DWKL EXHAUST DUCT BEARS ONLY THE UL
 1978 LISTING WHICH MAKES IT SUITABLE FOR USE AS A
 "GREASE DUCT" BUT DOES NOT HAVE THE UL 2221 LISTING AS
 A GREASE DUCT ENCLOSURE- PLEASE SEE SECTIONS 506.3.1.1
 AND 506.3.11.3 FBC-14 MECHANICAL.
  
 2) REFER TO TABLE 1-2 ON PAGE 5 OF THE INSTRUCTIONS:
 THE EXHAUST DUCTS ARE REQUIRED TO HAVE MINIMUM 2 INCHES
 OF CLEARANCE TO COMBUSTIBLE CONSTRUCTION. PLEASE NOTE
 THAT THE APPROVED M1.1 PLAN SHEET FOR THE RESTAURANT
 UNDER PERMIT #17020623 INDICATES THE GREASE DUCT TO BE
 A "ZERO CLEARANCE". ZERO CLEARANCE DUCTS TYPICALLY HAVE
 THE UL 2221 LISTING WHICH CLASSIFIES THOSE GREASE DUCTS
 AS "ENCLOSURES". PLEASE SUBMT A REVISED M1.1 PLAN SHEET
 THAT SHOWS THE CORRECT EXHAUST DUCTS TPO BE USED.
  
 3) SHOW THE LOCATIONS OF REQUIRED CLEANOUTS ON THE
 VERTICAL AND HORIZONTAL EXHAUST DUCT RUNS, AND PROVIDE
 ACCESS PANEL DETAILS FOR BOTH THE DUCTS AND THE DUCT
 ENCLOSURES- SEE PAGE 6 OF THE INSTALLATION
 INSTRUCTIONSA, AND SECTION 506.3.8 & 506.3.9.
  
 4) THE WIND LOAD ENGINEERING FOR ATTACHING THE GREASE
 DUCTS TO THE ROOF AND THE FANS TO THE DUCTS IS
 INCOMPLETE. THE CALCULATIONS AND ENGINEERING SHOW HOW
 THE FANS AND CURBS WILL BE ATTACHED TO THE STRUCTURE,
 HOWEVER THERE ARE NO DETAILS INDICATING HOW THE FANS
 WILL BE ATTACHED TO THE DUCTS AND HOW THE THE ENTIRE
 ASSEMBLIES INCLUDING THE DUCTS WILL BE ATTACHED TO THE
 ROOF STRUCTURE. PLEASE PROVIDE DETAILS THAT DEPICT THE
 ACTUAL FIELD CONDITIONS.
  
 5) PROVIDE UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLIES FOR SEALING THE EXHAUST DUCT PENETRATIONS-
 SECTION 506.3.11.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  