| Plan Review Notes For Permit 17100350 |
| Permit Number |
17100350 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-11 15:56:18 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) PROVIDE MANUFACTURES SPEC SHEETS FOR FIRE INSPECTOR | | | REVIEW ON INSPECTION. | | | | | | | | | | | | 2) PROVIDE FOR A MANUAL ACTIVATION DEVICE PER NFPA 96 | | | | | | 10.5 MANUAL ACTIVATION. | | | 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION | | | SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. | | | AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT | | | OF A FIRE, BE LOCATED IN A PATH OF EGRESS, AND CLEARLY | | | IDENTIFY THE HAZARD PROTECTED. | | | 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE | | | LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M | | | (20 FT) FROM THE PROTECTED KITCHEN APPLIANCE(S) WITHIN | | | THE PATH OF EGRESS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|