Plan Review Notes
Plan Review Notes For Permit 17100342
Permit Number 17100342
Review Stop B
Sequence Number 2
Notes
Date Text
2017-12-11 07:56:212014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100342
 ADD: 2701 OKEECHOBEE BLVD.
 CONT: RJS CONSTRUCTION GROUP
 TEL: 561-795-4712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. 11/ 2017
 ORIGINAL STRUCTURE BUILT/ C.O. 1963
 ACTION: DENIED
  
  
 1-2) COMPLIED.
 3) PLEASE NOTE THIS BUILDING WAS BUILT IN 1963 AND WITH
 AN ELEVATOR SINCE A PORTION OF THE BUILDING IS A 4
 STORY BUILDING. THE VALUE OF THIS PERMIT IS STATED AT
 $105,000.00 DOLLARS. WORK IS CURRENTLY ONLY SHOWING ON
 THE 2ND FLOOR LEVEL BUT THE VIOLATION OCCURS ON FLOORS
 2-4, NO AREA OF REFUGE. THE ACCESSIBILITY CODE
 CAN REQUIRE UP TO 20% OF THE CONTRACT VALUE FOR
 ACCESSIBILITY UPGRADES ($21,000.00) SEE :
  
 2014 FBC-EXISTING BUILDING CODE SECTION 806.1
 ABUILDING, FACILITY OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS AND
 SEE IN THE EVENT OF DISPROPORTIONALITY.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 ON THE 2ND FLOOR LEVEL THE PLANS DO NOT SHOW AN AREA OF
 REFUGE. THE 2014 ACCESSIBILITY CODE DOES REFER BACK TO
 THE 2003 IBC-B SECTION 1007. 207.1. MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION) (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1).
  
 3A) 2ND REQUEST. 2003 IBC-B 1007.6.1. SIZE. EACH AREA
 OF REFUGE SHALL BE SIZED TO ACCOMMODATE ONE WHEEL CHAIR
 SPACE OF 30 X 48 INCHES FOR EACH 200 OCCUPANTS.
  
 3B) 2ND REQUEST. 2003 IBC-B 1007.6.2. SEPARATION. EACH
 AREA OF REFUGE SHALL BE SEPARATED FROM THE REMAINDER OF
 THE STORY BY A SMOKE BARRIER COMPLYING WITH 709. EACH
 AREA OF REFUGE SHALL BE DESIGNED TO MINIMIZE THE
 INTRUSION OF SMOKE.
  
 3C) 2ND REQUEST. 2003 IBC-B 1007.6 .3 TWO-WAY
 COMMUNICATION. AREAS OF REFUGE SHALL BE PROVIDED WITH
 TWO-WAY COMMUNICATION SYSTEM BETWEEN THE AREA OF REFUGE
 AND A CONTROL POINT. IF THE CENTRAL CONTROL POINT IS
 NOT CONSTANTLY ATTENDED, THE AREA OF REFUGE SHALL ALSO
 HAVE CONTROLLED ACCESS TO A PUBLIC TELEPHONE SYSTEM.
 LOCATION OF THE CENTRAL CONTROL POINT SHALL BE APPROVED
 BY THE FIRE DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM
 SHALL INCLUDE BOTH AUDIBLE AND VISIBLE SIGNALS.
  
 3D)2ND REQUEST. 1007.6.4 INSTRUCTIONS. IN AREAS OF
 REFUGE THAT HAVE A TWO-WAY EMERGENCY COMMUNICATIONS
 SYSTEM, INSTRUCTIONS ON THE USE OF THE AREA UNDER
 EMERGENCY CONDITIONS SHALL BE POSTED ADJOINING THE
 COMMUNICATIONS SYSTEM. THE INSTRUCTIONS SHALL INCLUDE
 ALL OF THE FOLLOWING;
 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS.
 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON
 AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS.
 3) INFORMATION ON THE PLANNED AVAILABILITY OF
 ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION
 OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4)
 DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS
 SYSTEM.
  
 3E) 2ND REQUEST. 1007.6.5 IDENTIFICATION. EACH DOOR
 PROVIDING ACCESS TO AN AREA OF REFUGE FROM AN ADJACENT
 FLOOR AREA SHALL BE IDENTIFIED BY A SIGN COMPLYING WITH
 ICC A117., STATING AREA OF REFUGE, AND INCLUDING THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY. WHERE EXIT SIGN
 ILLUMINATION IS REQUIRED BY SECTION 1011.2, THE AREA OF
 REFUGE SIGN SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE
 SIGNAGE COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT
 EACH DOOR TO AN AREA OF REFUGE.
  
 3F) 2ND REQUEST. 1007.7. SIGNAGE. AT EXITS AND
 ELEVATORS SERVING A REQUIRED ACCESSIBLE SPACE BUT NOT
 PROVIDING AN APPROVED ACCESSIBLE MEANS OF EGRESS,
 SIGNAGE SHALL BE INSTALLED INDICATING THE LOCATION OF
 ACCESSIBLE MEANS OF EGRESS.
  
 4-6) COMPLIED.
  
 7) SEMI-COMPLIED. THE NEW HANDRAIL AND GUARDRAIL SYSTEM
 STOPS SHORT OF THE FLOOR LEVEL, BOTH STOP ATOP THE 1ST
 STEP ON THE LEVEL SURFACE. THE PLANS HAVE A NOTE TO
 MAINTAIN 4 FOOT MINIMUM BETWEEN THE TEMPERED GLASS WALL
 AND THE GUARDRAIL/ HANDRAIL. PLEASE CONSIDER PUTTING
 THE STAIRS BEHIND THE LIFT, SWOOP POSITIONS, THEN THE
 HANDRAIL ARE TO CONTINUE THE SLOPE ONE TREAD DISTANCE
 PAST THE FIRST RISER, NO HORIZONTAL EXTENSION IS
 REQUIRED, THE LIFT IS THE ACCESSIBLE MEANS OF EGRESS TO
 THE UPPER LEVEL. SEE 1012.6 HANDRAILS.
  
 1ST ROUND OF COMMENTS. SHEET A2.0 IN NOTE 10 INDICATES
 A NEW 42 INCH HIGH RAILING, THE PLAN DOES NOT INDICATE
 A GUARD RAIL AND NO INDICATION OF A HANDRAIL.
  
 7A) THE GUARDRAIL IS INDICTED TO START ON TOP OF THE
 FIRST RISER. PLEASE REFER TO THE 2014 FBC-B 1013.3
 HEIGHT. REQUIRED GUARDS SHALL NOT BE LESS THAN 42
 INCHES HIGH, MEASURED VERTICALLY AS FOLLOWS ;
 (1) FROM THE ADJACENT WALKING SURFACE, THE GUARDRAIL
 SHOULD CONTINUE OUT PAST THE STAIR THE WIDTH OF THE
 STAIR.
  
 7B THE NEW EXTERIOR DESIGN DOES NOT INDICATE THE TYPE
 OF STAIR CONCRETE OR STEEL, LIVE LOADS REQUIRED (TABLE
 1607.1) THE HEIGHT OF THE TOTAL RISE, RISE AND RUN OF
 THE TREAD OR RISER NOR THE WIND DESIGN CRITERIA FOR THE
 EXTERIOR STAIR NOR NOTAGE FOR THE REQUIREMENTS FOR THE
 HANDRAILS UNDER FBC-B 1012 OR GUARDS UNDER SECTION 1013
 FOR GUARDS. . PLEASE NOTE THERE IS NO FOUNDATION NOTE
 OR ANCHORING FOR THE NEW EXTERIOR STAIR. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRE.
  
 7C)COMPLIED. SHEET A2.1 DOES SHOW AN APPROVED GUARDRAIL
 SYSTEM FOR THE ROOF TOP EQUIPMENT.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved