Plan Review Notes
Plan Review Notes For Permit 17100342
Permit Number 17100342
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-10-12 10:33:442701 OKEECHOBEE BOULEVARD
 PERMIT #17100342
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THE ADDRESS OF THE PROJECT IS
 OKEECHOBEE ROAD AND THE PERMIT APPLICATION INDICATES
 THE ADDRESS IS OKEECHOBEE BOULEVARD. PLEASE COORDINATE
 THE CORRECT ADDRESS.
  
 LOFT SPACE RESULTS IN A COMMON PATH OF TRAVEL WITH
 TRAVEL DISTANCES EXCEEDING THOSE LIMITS PERMITTED BY
 THE FLORIDA FIRE PREVENTION CODE. BELOW ARE THE OPTIONS
 PERMITTED BY THE FFPC:
  
 38.2.4 NUMBER OF MEANS OF EGRESS.
 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING, EXCEPT AS OTHERWISE PERMITTED BY 38.2.4.2
 THROUGH 38.2.4.6:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY PART OF EVERY STORY.
 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL
 BE PERMITTED TO INCLUDE A SINGLE EXIT ACCESS PATH FOR
 THE DISTANCES PERMITTED AS COMMON PATHS OF TRAVEL BY
 38.2.5.3.
 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A TOTAL OCCUPANT LOAD OF LESS THAN 100
 PERSONS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF EXIT DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL WITHIN THE EXIT, SHALL NOT EXCEED 100
 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 38.2.4.3(2) SHALL BE ON THE SAME STORY, OR, IF
 TRAVERSING OF STAIRS IS NECESSARY, SUCH STAIRS SHALL
 NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE
 FOLLOWING ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO SEPARATE THEM FROM ANY OTHER PART OF THE
 BUILDING, WITH NO DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE PERMITTED TO SERVE ALL STORIES PERMITTED
 WITHIN THE 15 FT (4570 MM) VERTICAL TRAVEL LIMITATION.
  
 38.2.4.4 ANY BUSINESS OCCUPANCY THREE OR FEWER STORIES
 IN HEIGHT, AND NOT EXCEEDING AN OCCUPANT LOAD OF 30
 PEOPLE PER STORY, SHALL BE PERMITTED A SINGLE SEPARATE
 EXIT TO EACH STORY, PROVIDED THAT ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE.
 (2) THE TOTAL TRAVEL DISTANCE TO THE OUTSIDE OF THE
 BUILDING SHALL NOT EXCEED 100 FT (30 M).
 (3) INTERIOR EXIT STAIRS SHALL BE ENCLOSED IN
 ACCORDANCE WITH 7.1.3.2, AND BOTH OF THE FOLLOWING ALSO
 SHALL APPLY:
 (A) THE STAIR SHALL SERVE AS AN EXIT FROM NO OTHER
 STORIES.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE PERMITTED TO SERVICE ALL STORIES.
  
 38.2.4.5 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED
 FROM A MEZZANINE WITHIN A BUSINESS OCCUPANCY, PROVIDED
 THAT THE COMMON PATH OF TRAVEL DOES NOT EXCEED 75 FT
 (23 M), OR 100 FT (30 M) IF PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.7.1.1(1).
  
 38.2.4.6 A SINGLE EXIT SHALL BE PERMITTED FOR A
 SINGLE-TENANT SPACE OR BUILDING TWO OR FEWER STORIES IN
 HEIGHT, PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.7.1.1(1).
 (2) THE TOTAL TRAVEL TO THE OUTSIDE DOES NOT EXCEED 100
 FT (30 M).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  