| 2018-01-09 15:49:17 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- THE VALUE OF THE IMPROVEMENT IS MORE THAN $300.000. |
| | NEED TO COMPLY WITH THE ROOF TO WALL CONNECTIONS |
| | ACCORDING TO SEC. 708.8 OF FBC-EXISTING BUILDING CODE, |
| | 5TH EDITION (2014). SHOW COMPLIANCE. |
| | |
| | RESPONSE: |
| | A) THE COST ESTIMATE LETTER FROM HORIZON CUSTOM BUILDER |
| | INC. TO PROVIDE ROOF TO WALL CONNECTIONS IS INCORRECT. |
| | THE LETTER IS REFERENCING A BUILDING WITH 12 CORNERS. |
| | THERE ARE TWO BUILDINGS IN THIS PROPERTY. THE ROOFING |
| | PERMIT APPLICATION IS FOR THE REAR BUILDING AND IT |
| | DOESN'T HAVE 12 CORNERS. REVISE LETTER AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) NEED TO PROVIDE MORE DETAILED DESCRIPTION OF HOW THE |
| | FOUR CORNERS OF THE BUILDING ARE GOING TO BE STRAPPED. |
| | CLEARLY IDENTIFY SPECIFIC STRAP TO BE INSTALLED AND |
| | NUMBER OF STRAPS AND NAILS PER CORNER. NOTE: ACCORDING |
| | TO FIGURE R301.2(7) CORNERS ARE 4'-0" X 4'-0" MINIMUM. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | C) LETTER SUBMITTED DOESN'T HAVE ANY SIGNATURE. THE |
| | LETTER NEEDS TO BE SIGNED BY THE PERSON RESPONSIBLE FOR |
| | THE ESTIMATE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | |