| Plan Review Notes For Permit 17100302 |
| Permit Number |
17100302 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-25 17:47:25 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100302 | | | 10/25/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M.1, OUTDOOR AIR CALCULATION: O/A FOR | | | PROCEDURE ROOMS ARE CALCULATED AT 15 CFM PER PERSON- | | | PLEASE CORRECT. | | | | | | 2) M.1: THE 8" RETURN TRANSFER DUCT IS UNDERSIZED PER | | | SECTION 601.5 (1). A 10" DUCT IS REQUIRED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|