| Plan Review Notes For Permit 17100299 |
| Permit Number |
17100299 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-04-09 17:24:31 | ****PROVISOS**** | | | | | | 1. PROVIDE 2 SETS OF TRUSS DRAWINGS WITH THE ENGINEER | | | OF RECORD APPROVAL AT INSPECTION. | | | | | | 2. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | | RECORD. AFTER THAT REVIEW, SUBMIT FOR REVIEW BY THE | | | BUILDING DIVISION. | | | | | | 3. WINDOW AND DOOR OPENINGS ARE TO COMPLY WITH R703.8 | | | FLASHING. | | | APPROVED CORROSION-RESISTANT FLASHING SHALL BE APPLIED | | | SHINGLE-FASHION IN A MANNER TO PREVENT ENTRY OF WATER | | | INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE | | | BUILDING STRUCTURAL FRAMING COMPONENTS. SELF-ADHERED | | | MEMBRANES USED AS FLASHING SHALL COMPLY WITH AAMA 711. | | | ALL EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT | | | THE JUNCTURE WITH THE BUILDING WALL WITH A SEALANT | | | COMPLYING WITH AAMA 800 OR ASTM C 920 CLASS 25 GRADE NS | | | OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION, | | | ASTM C 1281, AAMA 812, OR OTHER APPROVED STANDARD AS | | | APPROPRIATE FOR THE TYPE OF SEALANT. THE FLASHING SHALL | | | EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH. | | | | | | PROVIDE A DETAIL AT INSPECTION. SUBJECT TO INSPECTOR'S | | | DISCRETION, A REVISION (WITH FEES) MAY BE REQUIRED. | | | | | | | | | |
|