| 2018-03-12 12:35:37 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE - BUILDING INSPECTOR |
| | 561-805-6667 [email protected] |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| | RESIDENTIAL CODE 2015 5TH EDITION |
| | |
| | SECOND REVIEW: |
| | |
| | |
| | 1. PARTIALLY ADDRESSED, DESIGNER OF RECORD HAS NOT |
| | APPROVED THE TRUSS DOCUMENTS. |
| | |
| | PROVIDE 2 SETS OF TRUSS DRAWINGS WITH THE ENGINEER OF |
| | RECORD APPROVAL. |
| | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS. |
| | |
| | |
| | 2. OK ADDRESSED. |
| | |
| | IMPACT FEES |
| | |
| | |
| | 3. PARTIALLY ADDRESSED. |
| | |
| | A. MULLION PRODUCT APPROVAL NOT PROVIDED. |
| | B. THE DESIGNER OF RECORD HAS NOT APPROVED THE PRODUCT |
| | APPROVALS. |
| | C. SELECT THE ASSEMBLY USED FOR THE CERTAIN TEED |
| | ROOFING TO BE USED. ONCE THE ASSEMBLY IS SELECTED, SEE |
| | THE LIMITATIONS ON PAGE 19. IF LIMITATION NUMBER 7 IS |
| | APPLICABLE ADDITIONAL ENHANCED UPLIFT CALCULATIONS WILL |
| | BE REQUIRED. |
| | |
| | PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE |
| | FOLLOWING: |
| | ROOFING PRODUCTS, DOORS, WINDOWS AND MULLIONS AND |
| | SHUTTERS IF APPLICABLE. |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR |
| | SUBMITTALS. |
| | |
| | 4. OK. ADDRESSED PERMIT VALUE ADJUSTED AS SUBMITTED. |
| | |
| | PLEASE ADJUST THE PERMITTED VALUE TO INCLUDE ALL |
| | MATERIALS AND LABOR. |
| | |
| | |
| | 5. NOT ADDRESSED. INCLUDE THIS ON THE TYPICAL WALL |
| | SECTION ON A 301. |
| | SHOW HOW THE WINDOW AND DOOR OPENINGS WILL COMPLY WITH |
| | THIS SECTION. |
| | R703.8 FLASHING. |
| | APPROVED CORROSION-RESISTANT FLASHING SHALL BE APPLIED |
| | SHINGLE-FASHION IN A MANNER TO PREVENT ENTRY OF WATER |
| | INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE |
| | BUILDING STRUCTURAL FRAMING COMPONENTS. SELF-ADHERED |
| | MEMBRANES USED AS FLASHING SHALL COMPLY WITH AAMA 711. |
| | ALL EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT |
| | THE JUNCTURE WITH THE BUILDING WALL WITH A SEALANT |
| | COMPLYING WITH AAMA 800 OR ASTM C 920 CLASS 25 GRADE NS |
| | OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION, |
| | ASTM C 1281, AAMA 812, OR OTHER APPROVED STANDARD AS |
| | APPROPRIATE FOR THE TYPE OF SEALANT. THE FLASHING SHALL |
| | EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH. |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | ********************* |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | ********************* |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |