| 2017-11-06 15:50:26 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| | 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC |
| | 107.2.1 |
| | 2. NOTE 13 STATES THAT WIRING TO BEDROOMS SHOULD BE |
| | AFCI PROTECTED. THIS IS NOT THE FULL EXTENT OF THE CODE |
| | REQUIREMENT: "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 |
| | AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING |
| | UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| | LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, |
| | CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL |
| | HAVE AFCI PROTECTION". PROVIDE CORRECTION IN NOTES, |
| | PANEL SCHEDULE, AND PLAN. NEC 210.12; FBC RE3902.12 |
| | 3. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 |
| | 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. PROVIDE ENTIRE FLOOR PLAN SHOWING ALL |
| | EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| | SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1 |
| | 5. PROVIDE ACCURATE LOAD CALCULATION. THE FIRST 10KW |
| | SHOULD BE FIGURED AT 100%, NOT 10%. VOLTAGE FOR SINGLE |
| | PHASE SERVICE TO A RESIDENCE IS 240 VOLT. PROVIDE |
| | CORRECTIONS. NEC 220; FBC RE 3602.2; FBC 107.2.1 |
| | 6. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE |
| | CORRECTION. THE BATH MARKED ROOM 104 DOES NOT SHOW THIS |
| | REQUIRED RECEPTACLE. PROVIDE CORRECTION. NEC |
| | 210.11(C)(3), 210.52(D); FBC RE 3703.4, 3901.6 |
| | 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 8. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | 9. KITCHEN COUNTER RECEPTACLE OUTLETS REQUIRE A MINIMUM |
| | OF TWO SMALL APPLIANCE CIRCUITS. PANEL SCHEDULE ONLY |
| | SHOWS ONE. PROVIDE CORRECTION. FBC RE 3703.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |