Plan Review Notes
Plan Review Notes For Permit 17100298
Permit Number 17100298
Review Stop P
Sequence Number 2
Notes
Date Text
2018-03-01 17:48:5403/01/2018 PLUMBING 2ND REVIEW**DENIED**
  
 1) TANKLESS WATER HEATER RTEX-18 WOULD BE UNDERSIZED AS
 PER THE CHART PROVIDED @ 36 DEGREE HEAT RISE HOT WATER
 (110 DEGREES) WOULD NOT BE ABLE TO FLOW HOT WATER TO
 ALL FIXTURES AT FULL DEMAND AS REQUIRED IN FBC-R
 P2801.1
  
 2) SHT P 2.0 IS SHOWING A STORAGE TYPE 80 GALLON HOT
 WATER HEATER. PROVIDE MANUFACTURES SPECS SHEETS SHOWING
 WATER HEATER MEETS THE REQUIRED 1.96 E.F AS REQUIRED BY
 THE D.O.E (NAECA) STANDARD AS OF 04/15/2015. LIGHT DUTY
 COMMERCIAL HEATERS ARE PROHIBITED TO BE USED IN
 RESIDENTIAL OCCUPANCY. THE LARGEST NON-HEAT PUMP
 STORAGE WATER HEATER ALLOWED IS 55 GALLONS.
  
 3) SHT P-1.0 NOTE #8 PLEASE INPUT HAMMER ARRESTORS
 REQUIRED AT ALL QUICK CLOSING VALVES. FBC-R P2903.5.
  
 4) YOUR WATER DISTRIBUTION ISOMETRIC DRAWING IS SHOWING
 C.P.V.C BUT SHT. P-1.0 NOTE #2 AND #6 CALL OUT MATERIAL
 TO BE COPPER ONLY. FBC 105.1
  
 5) BACKFLOW SHOWING ON SHT. P-1.0 FOR POOL AUTOFILL
 PLEASE ADD NOTE SEPARATE PERMIT REQUIRED AND BACKFLOW
 TO BE LEAD-FREE. ALSO A BACKFLOW (RPZ) IS REQUIRED AT
 THE WATER METER TO PROTECT THE CITY?S WATER SUPPLY PER
 WPB CROSS CONNECTION MANUAL.
  
 6) SANITARY ISOMETRIC ON SHT. P-2.0 IS STILL SHOWING A
 FLAT, DRY VENT ON THE SHOWER OF THE UN-NUMBERED
 BATHROOM ON THE 1ST FLOOR. FBC-R P3104.3
  
 7) SHT. P-1.0 CONFLICTS WITH SHT. P-2.0 IN REGARDS TO
 BOTH WATER AND SANITARY PIPE SIZING. P-1.0 STILL SHOWS
 2? PVC TO TOILET WHICH IS UNDERSIZED. FBC-R P3005.4.1
  
 8) PLEASE SHOW P-TRAPS ON ALL TUBS, BIDETS, AND SHOWER
 AS REQUIRED IN FBC-R P3201.6
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  