Plan Review Notes
Plan Review Notes For Permit 17100298
Permit Number 17100298
Review Stop E
Sequence Number 2
Notes
Date Text
2018-02-16 13:40:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16; FBC RE E4003.12
 2. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. SEVERAL AREAS
 SHOW THE BATHROOM RECEPTACLES TIED TO CIRCUITS OUTSIDE
 THE BATHROOM. PROVIDE CORRECTION. NEC 210.11(C)(3) ,
 FBC RE E3703.4
 3. DINING ROOM LIGHT IS SHOWN ON THE SAME CIRCUIT AS
 THE DINING ROOM RECEPTACLE OUTLETS, WHICH IS A CODE
 VIOLATION. PROVIDE CORRECTION. NEC 210.52(B)(2); FBC RE
 E3703.2
 4. CONFLICT EXIST BETWEEN THE PANEL SCHEDULE AND THE
 RISER DIAGRAM. PANEL A SCHEDULE SHOWS THAT PANEL B IS
 BEING FED FROM PANEL A, BUT THE RISER SHOWS THAT IT TIS
 BEING FED FROM A METER MAIN COMBO. CLARIFY AND/OR
 CORRECT. NEC 215.5; FBC 107.2.1
 5. PANEL B IS SHOWN AS BEING FED WITH 2/0 WIRE ON A 60
 AMP BREAKER. A 60 AMP BREAKER WILL NOT ACCOMMODATE THIS
 WIRE SIZE. PROVIDE CORRECTION. NEC 110.3
 6. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH WOULD REQUIRE A 25 AMP BREAKER.
 PROVIDE CORRECTION. NEC 422.13; FBC RE E3702.10
 7. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 8. A CONFLICT EXIST IN NOTE 49 WHICH CALLS FOR
 COMPLIANCE WITH THE 2005 NEC AND THE 2014 FBC. THE 2014
 FBC REFERENCES THE 2011 NEC. PROVIDE CORRECTION. FBC
 PREFACE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  