| Date |
Text |
| 2017-11-02 13:30:20 | 1) SHT. A-3.0 - SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATION SHEETS FOR THE CHLORALOY SHOWER PAN |
| | MATERIAL. THE MATERIAL SHALL COMPLY WITH ASTM D 4068 |
| | FOR CHLORINATED POLYETHYLENE (CPE) SSHEETS. 2014 FBCR |
| | SEC. P2709.2.2. |
| | 2) THE WATER HEATER IN THE GARAGE SHALL BE PROTECTED |
| | FROM PHYSICAL DAMAGE.SUBMIT DETAILS AS TO HOW |
| | PROTECTION WILL BE PROVIDED. 2014 FBCR SEC. 1307.3.1. |
| | 3) THE PLANS SHOW A GAS FIREPLACE. A SEPARATE PERMIT |
| | APPLICATION AND 2 SETS OF PLANS SHALL BE SUBMITTED FOR |
| | THE GAS SYSTEM AND MANUFACTURER'S SPECIFICATIONS SHALL |
| | BE SUBMITTED FOR THE FIREPLACE.. |
| | 4) SHOW THE REQUIRED PLUMBING FIXTURE CLEARANCES ON THE |
| | FLOOR PLAN. COMPLY WITH THE 2014 FBCR SEC.P2705.1. SHOW |
| | THE LENGTH AND WIDTH OF THE SHOWERS. COMPLY WITH 2014 |
| | FBCR SEC.P2708.1. |
| | 5) THE TERMINATION OF THE WATER HEATER PAN DRAIN SHALL |
| | COMPLY WITH 2014 FBCR SEC.P2801.5.2. |
| | 6) SHT. P-1.0 - PLUMBING NOTE #8 - AIR CHAMBERS ARE NOT |
| | APPROVED FOR THE CONTROL OF WATER HAMMER. WATER - |
| | HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010. 2014 FBCR |
| | SEC.P2903.5. |
| | 7) SHT. P-1.0 - THE PLANS SHOW PVC USED FOR SOME OF THE |
| | WATER DISTRIBUTION SYSTEM.PVC PIPE IS NOT PERMITTED TO |
| | BE USED IN THE WATER DISTRIBUTION SYSTEM PER 2014 FBCR |
| | SEC. P2905.5 & TABLE P2905.5. |
| | 8) SHT. P-1.0 SHOWS A 1 INCH WATER LINE TO THE POOL |
| | PUMP SYSTEM.THIS IS NOT SHOWN ON THE WATER RISER. |
| | CLARIFY ON THE PLANS WHAT THIS LINE IS FOR. A BACKFLOW |
| | PREVENTER MAY BE REQUIRED ON THIS LINE. |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATER SHOWN ON THE FIRST FLOOR. IT IS |
| | NOT SHOWN ON THE ELECTRIC PLAN. IS IT GAS? CLARIFY. |
| | 10) SHT. P-2.0 - GROUND FLOOR SANITARY WASTE RISER - |
| | FLAT, DRY VENTS ARE NOT PERMITTED PER 2014 FBCR SEC. |
| | P3104.3. |
| | 11) SHT. P-2.0 - FIRST FLOOR SANITARY WASTE RISER - |
| | FLAT, DRY VENTS NOT PERMITTED AND THE DOUBLE LAVATORIES |
| | ARE NOT VENTED PER THE PLUMBING CODE. 2014 FBCR |
| | SEC.P3104.3, P3101.2.1. |
| | 12) SHT. P-2.0 - GROUND FLOOR SANITARY RISER SHOWS A 1 |
| | 1/2 INCH DRAIN FOR THE LAVATORY AND WATER CLOSET FOR |
| | THE POWDER ROOM. THE MINIMUM SHALL BE 3 INCHES. 2014 |
| | FBCR SEC.P3005.4.1. |
| | 13) THE WATER RISER IS MISSING PIPE SIZES. SIZE THE |
| | WATER RISER. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |