| 2017-10-30 16:02:36 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE SIZE OF ALL OF THE DUCTS ON THE PLANS. | | | SOME OF THE DUCTS ARE MISSING THE SIZES. FBC 107.3.5.3 | | | | | | 2) SHOW THE RETURN AIR GRILLS AND DUCTS ON THE PLANS. | | | SPECIFY THE RETURN AIR DUCT AND GRILL SIZES ON THE | | | PLANS. FBC 107.3.5.3 | | | | | | 3) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED | | | RETURN AIR AT THE BEDROOMS. ALL AIR SUPPLY INTO THE | | | MASTER SUITE IS REQUIRED TO BE INCLUDED FOR BALANCED | | | RETURN AIR. | | | |
|