2017-10-30 16:02:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE SIZE OF ALL OF THE DUCTS ON THE PLANS.
 SOME OF THE DUCTS ARE MISSING THE SIZES. FBC 107.3.5.3
  
 2) SHOW THE RETURN AIR GRILLS AND DUCTS ON THE PLANS.
 SPECIFY THE RETURN AIR DUCT AND GRILL SIZES ON THE
 PLANS. FBC 107.3.5.3
  
 3) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED
 RETURN AIR AT THE BEDROOMS. ALL AIR SUPPLY INTO THE
 MASTER SUITE IS REQUIRED TO BE INCLUDED FOR BALANCED
 RETURN AIR.
  