| 2017-10-16 15:04:54 | THIS PLAN HAS BEEN PASSED PROVISIONALLY. |
| | |
| | SMOKE ALARMS OUTSIDE OF BEDROOMS MUST ALSO BE CARBON |
| | MONOXIDE ALARMS. FBC-R 315.1 |
| | |
| | LAUNDRY RECEPTACLE FOR WASHER MUST BE GFCI PROTECTED IF |
| | WITHIN 6' OF SINK. NEC 210.8 (A7) |
| | |
| | RECEPTACLE NEEDED IN HALLWAY TO BEDROOM #1. NEC 210.52 |
| | (H) |
| | |
| | MASTER BATHROOM NEEDS SWITCH INSIDE ROOM FOR BATHROOM |
| | LIGHTING. NEC 210.70 (A1) |
| | |
| | NEED ADDITIONAL GFCI RECEPTACLE BY 2ND SINK IN MASTER |
| | BATH (WITHIN 3' OF SINK) NEC 210.52 (D). |
| | |
| | NO LOCATION OF PANEL B ON PLANS. PROVIDE AS-BUILT |
| | DRAWING SHOWING LOCATION OF PANEL B FOR FINAL. NEC |
| | 240.24 (D&E) CANNOT BE LOCATED IN BATHROOMS OR CLOSETS. |
| | |
| | FEEDER FOR PANEL B CANNOT BE ROMEX. SEE ELECTRICAL NOTE |
| | #8 ON PLAN. (ALL WIRING MUST BE IN METALLIC PIPE) |
| | |
| | BALCONY ADJACENT TO MASTER BEDROOM NEEDS W.P, GFCI |
| | RECEPTACLE. NEC 210.52 (E3) |
| | |
| | SMOKE ALARMS WILL BE 3' AWAY FROM FURTHEST POINT OF |
| | CEILING FAN BLADES. NFPA 72 29.8.3.4 (#7) |
| | |
| | INTERSYSTEM BONDING TERMINATION REQUIRED AT SERVICE |
| | (BONDING BRIDGE) NEC 250.94 |
| | |
| | PLAN HAS BEEN MARKED TO SHOW CORRECTIONS. |
| | |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | SINCERELY, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |