Plan Review Notes
Plan Review Notes For Permit 17100298
Permit Number 17100298
Review Stop E
Sequence Number 1
Notes
Date Text
2017-10-16 15:04:54THIS PLAN HAS BEEN PASSED PROVISIONALLY.
  
 SMOKE ALARMS OUTSIDE OF BEDROOMS MUST ALSO BE CARBON
 MONOXIDE ALARMS. FBC-R 315.1
  
 LAUNDRY RECEPTACLE FOR WASHER MUST BE GFCI PROTECTED IF
 WITHIN 6' OF SINK. NEC 210.8 (A7)
  
 RECEPTACLE NEEDED IN HALLWAY TO BEDROOM #1. NEC 210.52
 (H)
  
 MASTER BATHROOM NEEDS SWITCH INSIDE ROOM FOR BATHROOM
 LIGHTING. NEC 210.70 (A1)
  
 NEED ADDITIONAL GFCI RECEPTACLE BY 2ND SINK IN MASTER
 BATH (WITHIN 3' OF SINK) NEC 210.52 (D).
  
 NO LOCATION OF PANEL B ON PLANS. PROVIDE AS-BUILT
 DRAWING SHOWING LOCATION OF PANEL B FOR FINAL. NEC
 240.24 (D&E) CANNOT BE LOCATED IN BATHROOMS OR CLOSETS.
  
 FEEDER FOR PANEL B CANNOT BE ROMEX. SEE ELECTRICAL NOTE
 #8 ON PLAN. (ALL WIRING MUST BE IN METALLIC PIPE)
  
 BALCONY ADJACENT TO MASTER BEDROOM NEEDS W.P, GFCI
 RECEPTACLE. NEC 210.52 (E3)
  
 SMOKE ALARMS WILL BE 3' AWAY FROM FURTHEST POINT OF
 CEILING FAN BLADES. NFPA 72 29.8.3.4 (#7)
  
 INTERSYSTEM BONDING TERMINATION REQUIRED AT SERVICE
 (BONDING BRIDGE) NEC 250.94
  
 PLAN HAS BEEN MARKED TO SHOW CORRECTIONS.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  