| Plan Review Notes For Permit 17100292 |
| Permit Number |
17100292 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-17 13:49:14 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. MEP AND E SHEETS DO NOT SHOW PROJECT ADDRESS. | | | PROVIDE CORRECTION. FBC 107.2.1 | | | 2. PER THE INCLUDED SHEETS IN THE ELECTRICAL SHEET | | | INDEX, SHEET E5.1 IS MISSING. PROVIDE CORRECTION. FBC | | | 107.2.1 | | | 3. PERMIT APPLICATION AND PLAN STATES THAT THIS IS A | | | DEMO PLAN, BUT THERE ARE SEVERAL ELECTRICAL SHEETS | | | SHOWING NEW LIGHTING. REMOVE ANY SHEETS NOT RELEVANT TO | | | DEMO. FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|