2018-04-11 14:51:39****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
  
 CODE: FBC 5TH EDITION (2014).
 4/11/18 THIRD REVIEW:
  
 ADDRESSED COMMENTS HAVE BEEN REMOVED. NEW COMMENTS WILL
 APPEAR ON TOP OF EXISTING.
  
 5- DRAFTSTOPPING IN ATTIC NOT FOUND.
 PROVIDE DETAILS AND SPECIFICATIONS FOR DRAFSTOPPING ON
 THE SECOND FLOOR FRAMING PLAN AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL. AND INDICATE ON PLANS
 DRAFSTOPPING LOCATION.
 RESPONSE: REPEAT COMMENT.
  
 7- NOT PROVIDED.
 PROVIDE ICC EVALUATION REPORT FOR SPRAY INSULATION
 SPECIFIED FOR THE UNVENTED ATTIC. ARCHITECT TO
 REVIEW/APPROVE PRIOR TO SUBMITTAL. SEC. R316
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 8- NOT ADDRESSED.
 STRUCTURAL NOTES AND TRUSS DESIGN CRITERIA ON SHEET S2
 ARE REFERENCING ASCE 7-16. THE CURRENT ASCE 7 EDITION
 ADOPTED WITH THE 2014 FBC IS THE ASCE 7-10 NOT ASCE
 7-16. REVISE AS REQUIRED BY CHAPTER 46 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 9- NOT ADDRESSED. R405-2017 STILL USED.
 ENERGY CALCULATIONS SUBMITTED:
 A) NEW FORM R405-2017 WAS SUBMITTED. THIS FORM IS
 INCORRECT. THIS BUILDING IS BEING REVIEWED UNDER THE
 2014 FBC. NEED TO RE-SUBMIT THE FORM R405-2014 THAT WAS
 SUBMITTED THE FIRST TIME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 B) NUMBER OF BEDROOMS ON ITEM #4 IS INCORRECT. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) ROOF DECK INSULATION R-VALUE SPECIFIED ON ITEM #10
 IS INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 D) SPACES INFORMATION ON PAGE 2 OF 4 IS INCORRECT. NED
 TO INCLUDE THE KITCHEN AND CORRECT NUMBER OF BEDROOMS
 AND PEOPLE. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT.
 E) ROOF INFORMATION ON PAGE 2 OF 4 IS INCORRECT. REVISE
 AS REQUIRED TO MATCH PLANS. THE TYPE OF ROOF IS GABLE
 NOT HIP AND THE ROOF MATERIAL IS METAL ROOF NOT
 SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT.
 F) THE WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. REVISE THE WINDOWS ORIENTATION AND AREA TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT.
 I) PROVIDE THE COMPLETE INSPECTION CHECKLIST REQUIRED
 BY SEC. R405.4.2 (2) FBC-ENERGY CONSERVATION.
 REPEAT COMMENT.
 J) PROVIDE THE COMPLETE EPL DISPLAY CARD SIGNED BY THE
 BUILDER AS REQUIRED BY SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
 REPEAT COMMENT.
  
 10- ROUND WINDOW PRODUCT APPROVAL NOT PROVIDED.
  
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
  
 FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
  
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
  
 B) ROUND WINDOWS AS SHOWN ON PLANS. REPEAT COMMENT.
  
 E) RECEIVED PRODUCT APPROVAL. BUT IT IS FOR CONCRETE
 DECKS.
  
 BALCONY UNDERLAYMENT SPECIFIED ON PLANS. NOTE: NEED
 PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE TILE AS
 SPECIFIED ON PLANS. CLEARLY IDENTIFY SPECIFIC ASSEMBLY
 TO BE USED. IF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS WILL BE REQUIRED.
 RESPONSE: KEMPEROL MEMBRANE WATERPROOFING SYSTEM
 SUBMITTED IS FOR CONCRETE DECKS. THIS IS A WOOD DECK.
 PROVIDE PROPER PRODUCT APPROVAL. AND IDENTIFY SELECTED
 ASSEMBLY AS REQUESTED ABOVE.
  
  
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT ALL DRAWINGS
 FOR REFERENCE.
  
  
  