| 2018-04-11 14:51:39 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | 561-805-6718 [email protected] |
| | |
| | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | |
| | CODE: FBC 5TH EDITION (2014). |
| | 4/11/18 THIRD REVIEW: |
| | |
| | ADDRESSED COMMENTS HAVE BEEN REMOVED. NEW COMMENTS WILL |
| | APPEAR ON TOP OF EXISTING. |
| | |
| | 5- DRAFTSTOPPING IN ATTIC NOT FOUND. |
| | PROVIDE DETAILS AND SPECIFICATIONS FOR DRAFSTOPPING ON |
| | THE SECOND FLOOR FRAMING PLAN AS REQUIRED BY SEC. |
| | R302.12 FBC-RESIDENTIAL. AND INDICATE ON PLANS |
| | DRAFSTOPPING LOCATION. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 7- NOT PROVIDED. |
| | PROVIDE ICC EVALUATION REPORT FOR SPRAY INSULATION |
| | SPECIFIED FOR THE UNVENTED ATTIC. ARCHITECT TO |
| | REVIEW/APPROVE PRIOR TO SUBMITTAL. SEC. R316 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 8- NOT ADDRESSED. |
| | STRUCTURAL NOTES AND TRUSS DESIGN CRITERIA ON SHEET S2 |
| | ARE REFERENCING ASCE 7-16. THE CURRENT ASCE 7 EDITION |
| | ADOPTED WITH THE 2014 FBC IS THE ASCE 7-10 NOT ASCE |
| | 7-16. REVISE AS REQUIRED BY CHAPTER 46 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 9- NOT ADDRESSED. R405-2017 STILL USED. |
| | ENERGY CALCULATIONS SUBMITTED: |
| | A) NEW FORM R405-2017 WAS SUBMITTED. THIS FORM IS |
| | INCORRECT. THIS BUILDING IS BEING REVIEWED UNDER THE |
| | 2014 FBC. NEED TO RE-SUBMIT THE FORM R405-2014 THAT WAS |
| | SUBMITTED THE FIRST TIME. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | B) NUMBER OF BEDROOMS ON ITEM #4 IS INCORRECT. SEE |
| | PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | C) ROOF DECK INSULATION R-VALUE SPECIFIED ON ITEM #10 |
| | IS INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | D) SPACES INFORMATION ON PAGE 2 OF 4 IS INCORRECT. NED |
| | TO INCLUDE THE KITCHEN AND CORRECT NUMBER OF BEDROOMS |
| | AND PEOPLE. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | REPEAT COMMENT. |
| | E) ROOF INFORMATION ON PAGE 2 OF 4 IS INCORRECT. REVISE |
| | AS REQUIRED TO MATCH PLANS. THE TYPE OF ROOF IS GABLE |
| | NOT HIP AND THE ROOF MATERIAL IS METAL ROOF NOT |
| | SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | REPEAT COMMENT. |
| | F) THE WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH |
| | PLANS. REVISE THE WINDOWS ORIENTATION AND AREA TO MATCH |
| | PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | REPEAT COMMENT. |
| | I) PROVIDE THE COMPLETE INSPECTION CHECKLIST REQUIRED |
| | BY SEC. R405.4.2 (2) FBC-ENERGY CONSERVATION. |
| | REPEAT COMMENT. |
| | J) PROVIDE THE COMPLETE EPL DISPLAY CARD SIGNED BY THE |
| | BUILDER AS REQUIRED BY SEC. R405.4.3 FBC-ENERGY |
| | CONSERVATION. |
| | REPEAT COMMENT. |
| | |
| | 10- ROUND WINDOW PRODUCT APPROVAL NOT PROVIDED. |
| | |
| | ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED |
| | SUBMITTAL BY LISTING THEM ON THE COVER SHEET. |
| | |
| | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | |
| | B) ROUND WINDOWS AS SHOWN ON PLANS. REPEAT COMMENT. |
| | |
| | E) RECEIVED PRODUCT APPROVAL. BUT IT IS FOR CONCRETE |
| | DECKS. |
| | |
| | BALCONY UNDERLAYMENT SPECIFIED ON PLANS. NOTE: NEED |
| | PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE TILE AS |
| | SPECIFIED ON PLANS. CLEARLY IDENTIFY SPECIFIC ASSEMBLY |
| | TO BE USED. IF SELECTED ASSEMBLY DOESN'T MEET THE |
| | DESIGN PRESSURES FOR ALL ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS WILL BE REQUIRED. |
| | RESPONSE: KEMPEROL MEMBRANE WATERPROOFING SYSTEM |
| | SUBMITTED IS FOR CONCRETE DECKS. THIS IS A WOOD DECK. |
| | PROVIDE PROPER PRODUCT APPROVAL. AND IDENTIFY SELECTED |
| | ASSEMBLY AS REQUESTED ABOVE. |
| | |
| | |
| | |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT ALL DRAWINGS |
| | FOR REFERENCE. |
| | |
| | |
| | |