| Plan Review Notes For Permit 17100284 |
| Permit Number |
17100284 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-08 18:48:04 | 1- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) BALCONY UNDERLAYMENT SPECIFIED ON PLANS. NOTE: NEED | | | PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE TILE AS | | | SPECIFIED ON PLANS. CLEARLY IDENTIFY SPECIFIC ASSEMBLY | | | TO BE USED. IF SELECTED ASSEMBLY DOESN'T MEET THE | | | DESIGN PRESSURES FOR ALL ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS WILL BE REQUIRED. | | | RESPONSE: KEMPEROL MEMBRANE WATERPROOFING SYSTEM | | | SUBMITTED IS FOR CONCRETE DECKS. THIS IS A WOOD DECK. | | | PROVIDE PROPER PRODUCT APPROVAL. AND IDENTIFY SELECTED | | | ASSEMBLY AS REQUESTED ABOVE. | | | | | | | | | APPROVED PRODUCT APPROVALS; | | | A) 5V METAL ROOF NOA 13-0627.02 | | | B) METAL ROOF UNDERLAYMENT NOA 16-0322.26 |
|