| 2018-03-08 18:59:45 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL | | | REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED | | | ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED | | | BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | RESPONSE: REPEAT COMMENT. | | | | | | 2- A/C PLAN TO HAVE THE NAME AND SIGNATURE OF THE | | | CONTRACTOR RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | RESPONSE: REPEAT COMMENT. | | | | | | 3- NEED EXHAUST FAN FOR THE MASTER BATHROOM. ONLY ONE | | | EXHAUST FAN IS PROVIDED FOR THE WATER CLOSET | | | COMPARTMENT. REVISE AS REQUIRED. TABLE M1507.4 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | RESPONSE: REPEAT COMMENT. | | | | | | 4- SPECIFY CLOTHES DRYER EXHAUST AS REQUIRED BY SEC. | | | M1502 FBC-RESIDENTIAL. | | | RESPONSE: REPEAT COMMENT. | | | | | | *** PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT ALL DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|