Plan Review Notes
Plan Review Notes For Permit 17100284
Permit Number 17100284
Review Stop P
Sequence Number 1
Notes
Date Text
2017-11-03 10:38:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT P-1 NOTE #15 AIR CHAMBERS ARE NOT CODE COMPLIANT
 YOU SHALL USE WATER HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010. PER FBC ACC P2903.5
  
 2. THE WATER CLOSET IN BATHROOM 1 IS NOTE VENTED, THE
 TUB, WATER CLOSET AND LAVATORY SHOULD BE VENTED
 TOGETHER AS A WET VENT AND THEN CONNECTED TO BUILDING
 DRAIN. PER FBC RES P3108.1
  
 3. PLEASE SHOW LOCATION AND TYPE OF WATER HEATER. PER
 WPB AMEND TO FBC 107.2.1
  
 4. PROVIDE DETAIL FOR WATER HEATER PIPING. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  