2017-11-13 17:18:15NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED
 ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED
 BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: SEE BUILDING REVIEW COMMENTS REGARDING ENERGY
 CALCULATIONS REQUIRED REVISIONS.
  
 2- A/C PLAN TO HAVE THE NAME AND SIGNATURE OF THE
 CONTRACTOR RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS.
  
 3- A/C PLAN TO SHOW THE CFM'S ON ALL REGISTERS SHOWN ON
 PLANS. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- NEED EXHAUST FAN FOR THE MASTER BATHROOM. ONLY ONE
 EXHAUST FAN IS PROVIDED FOR THE WATER CLOSET
 COMPARTMENT. REVISE AS REQUIRED. TABLE M1507.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 5- SPECIFY CLOTHES DRYER EXHAUST AS REQUIRED BY SEC.
 M1502 FBC-RESIDENTIAL.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT ALL DRAWINGS
 FOR REFERENCE.
  